The numbers below refer to the step numbers on the diagnostic table.
This test resets the HVAC control processor and measures the current air temperature DTC.
This step tests for the proper operation of the coolant system to ensure heater output.
Step | Action | Values | Yes | No | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Schematic Reference: HVAC Schematics DEFINITION: The temperature can not be adjusted, or the heating is insufficient. | ||||||||||||||||
1 | Did you perform the HVAC Diagnostic System Check? | -- | Go to Step 2 | |||||||||||||
Does DTC B1340 or DTC B1341 set? | -- | Go to Step 3 | ||||||||||||||
3 | Place the blower motor switch in each speed position. Does the blower motor operate correctly for each speed position? | -- | Go to Step 4 | Go to Blower Motor Inoperative | ||||||||||||
4 | Does the blower motor provide sufficient airflow? | -- | Go to Step 5 | Go to Blower Motor Malfunction | ||||||||||||
5 |
Does the recirculation door move from the recirculation position to the outside air position? | -- | Go to Step 6 | |||||||||||||
6 | With the heater or with the defroster ON, does the customer concern occur? | -- | Go to Step 7 | Go to Step 8 | ||||||||||||
7 |
Does the A/C compressor operate? | -- | Go to Step 8 | |||||||||||||
8 |
Do the counts change when actuators are commanded? | -- | Go to Step 9 | Go to Step 16 | ||||||||||||
Inspect the cooling system for the following conditions:
Did you find and correct the condition? | -- | Go to Step 27 | Go to Step 10 | |||||||||||||
10 | Check the inside air temperature sensor for proper installation. Refer to Inside Air Temperature Sensor Replacement . Did you find and correct the condition? | -- | Go to Step 27 | Go to Step 11 | ||||||||||||
11 | Inspect for airflow through the inside air temperature sensor by placing a 5 cm (2 in) square piece of paper over the sensor air inlet. Does the paper stay in place? | -- | Go to Step 12 | Go to Step 18 | ||||||||||||
12 |
Does the scan tool indicate sensor temperatures near the thermometer temperatures within the specified range? | -3 to +3°C (-5 to +5°F) | Go to Step 13 | Go to Step 15 | ||||||||||||
13 |
Is the Solar Sensor parameter greater than the specified value? | 230 Counts | Go to Step 14 | Go to Step 21 | ||||||||||||
14 |
Do the counts change? | -- | Go to Testing for Intermittent Conditions and Poor Connections in Wiring Systems | Go to Step 21 | ||||||||||||
15 | Test the resistance at the inside air temperature sensor. Refer to Sensor Resistance Table . Is the resistance measurement near the value in the Sensor Resistance Table? | -- | Go to Step 22 | Go to Step 20 | ||||||||||||
16 | Test the suspected control circuit to the actuator door for an open, a high resistance, a short to power or a short to ground. Refer to Circuit Testing and Connector Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 27 | Go to Step 17 | ||||||||||||
17 | Test the ignition 3 voltage circuit on the suspected actuator for a short to ground, an open, or a high resistance. Refer to Circuit Testing and Connector Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 27 | Go to Step 19 | ||||||||||||
18 | Inspect the aspirator tube and the HVAC module for the following conditions:
Did you find and correct the condition? | -- | Go to Step 27 | -- | ||||||||||||
19 | Inspect for poor connections at the harness connector of the suspected air temperature sensor. Refer to Testing for Intermittent Conditions and Poor Connections and Connector Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 27 | Go to Step 25 | ||||||||||||
20 | Inspect for poor connections at the harness connector of the inside air temperature sensor. Refer to Testing for Intermittent Conditions and Poor Connections and Connector Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 27 | Go to Step 23 | ||||||||||||
21 | Inspect for poor connections at the harness connector of the sunload sensor. Refer to Testing for Intermittent Conditions and Poor Connections and Connector Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 27 | Go to Step 24 | ||||||||||||
22 | Inspect for poor connections at the harness connector of the HVAC control processor. Refer to Testing for Intermittent Conditions and Poor Connections and Connector Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 27 | Go to Step 26 | ||||||||||||
23 | Replace the inside air temperature sensor. Refer to Inside Air Temperature Sensor Replacement . Did you complete the replacement? | -- | Go to Step 27 | -- | ||||||||||||
24 | Replace the sunload sensor. Refer to Sun Load Sensor Replacement . Did you complete the replacement? | -- | Go to Step 27 | -- | ||||||||||||
25 |
Important: Perform the recalibration procedure for the air temperature actuator. Replace the suspected air temperature actuator. Refer to Air Temperature Actuator Replacement - Right Side or Air Temperature Actuator Replacement - Left Side . Did you complete the replacement? | -- | Go to Step 27 | -- | ||||||||||||
26 |
Important: Perform the recalibration procedure for the HVAC control processor. Replace the HVAC control processor. Refer to HVAC Control Processor Replacement . Did you complete the replacement? | -- | Go to Step 27 | -- | ||||||||||||
27 | Operate the system in order to verify the repair. Did you correct the condition? | -- | System OK | Go to Step 3 |