The A/C Refrigerant Pressure sensor is a sensor that changes resistance based upon refrigerant pressure. The PCM provides a 5 volt reference and ground. The A/C refigerant sensor signal varies between ground and 5 volts as refrigerant pressure varies. As A/C refrigerant pressure increases, voltage increases. As A/C refrigerant pressure decreases, voltage decreases. A short to ground or open condition would cause the A/C refrigerant pressure sensor signal to go low, setting DTC P0532.
The A/C refrigerant pressure sensor reading has been 0.10 volts or less.
• | The Malfunction Indicator Lamp (MIL) will not illuminate. |
• | No message will be displayed. |
• | A History DTC will clear after forty consecutive warm-up cycles with no failures of any non-emission related diagnostic test. |
• | A Last Test Failed (current) DTC will clear when the diagnostic runs and does not fail. |
• | Use a scan tool to clear DTCs. |
• | Interrupting PCM battery voltage may or may not clear DTCs. This practice is not recommended. Refer to Clearing Diagnostic Trouble Codes in PCM Description and Operation. |
Number(s) below refer to the step number(s) on the Diagnostic Table.
If the A/C refrigerant pressure sensor or circuitry are open, the A/C refrigerant pressure sensor parameter will read 0.0 to 0.10 volts.
Checking if circuitry from sensor to PCM is able to respond to a 5 volt signal on the A/C refrigerant pressure input. A reading of 4.5 to 5.12 volts means wiring and PCM are OK.
Step | Action | Value(s) | Yes | No |
---|---|---|---|---|
1 | Did you perform the Powertrain On-Board Diagnostic (OBD) System Check? | -- | ||
Is the value displayed the same or less than the value specified? | 0.10 volts | Fault not present. | ||
Is the value displayed higher than the value specified? | 4.5 volts | |||
4 |
Is the voltage the same or higher than the voltage specified? | 4.5 volts | ||
5 |
Is the resistance less than the value specified? | OL | ||
6 | Measure the resistance between PCM connector C1 terminal 56 and A/C refrigerant pressure sensor connector terminal C (harness side). Is the resistance more than the value specified? | 5 ohms | ||
7 |
Is the voltage higher than the value specified? | 0.1 volts | ||
8 |
Is the resistance more than the value specified? | 5 ohms | ||
9 |
Is the resistance less than the value specified? | OL | ||
10 | Repair the short to ground in the A/C refrigerant pressure sensor signal circuit. Is the repair complete? | -- | Go to Powertrain Control Module Diagnosis for Verify Repair | -- |
11 | Repair the open in the A/C refrigerant pressure sensor signal circuit. Is the repair complete? | -- | Go to Powertrain Control Module Diagnosis for Verify Repair | -- |
12 | Repair the open in the 5 Volt Reference circuit. Is the repair complete? | -- | Go to Powertrain Control Module Diagnosis for Verify Repair | -- |
13 | Repair short to ground in CKT(s) with low resistance. Is the repair complete? | -- | Go to Powertrain Control Module Diagnosis for Verify Repair | -- |
14 |
Was terminal contact repaired? | -- | Go to Powertrain Control Module Diagnosis for Verify Repair | |
15 | Replace the A/C refrigerant pressure sensor. Go to Air Conditioning (A/C) Refrigerant Pressure Sensor Replacement for repair instructions. Is the replacement complete? | -- | Go to Powertrain Control Module Diagnosis for Verify Repair | -- |
16 |
Was terminal contact repaired? | -- | Go to Powertrain Control Module Diagnosis for Verify Repair | |
17 | Replace the PCM. Refer to Powertrain Control Module Replacement . Is the replacement complete? | -- | Go to Powertrain Control Module Diagnosis for Verify Repair | -- |