Electronic Leak Detection Method
Caution: Do not operate the detector in a combustible atmosphere since its sensor
operates at high temperature. Personal injury or damage to the equipment may
result.
Perform a refrigerant leak
test on the system whenever you suspect a leak due to the following conditions:
• | A system indication of a low charge |
• | After any service operation which disturbs the following items: |
Many methods and special tools are available for this purpose.
Tools Required
J 39400
This type of leak detector is the most useful tool in locating refrigerant
leaks.
There are 3 settings:
The gross leak setting is for isolating very large leaks already found
in one of the other two settings. Ensure that the instrument is properly calibrated,
per the included instructions. Ensure that the detector is used in the proper
setting for the type of refrigerant system being tested. Place the detector
GAS switch in the R-134a setting prior to use.
Prior to beginning the test, ensure that the refrigerant system is sufficiently
charged for leak testing by measuring the static pressure using a gauge set.
System pressures above 50 psi are acceptable to conduct a leak test.
The most common leaks are found at the refrigerant fittings or connections.
Leaks may result from the following conditions:
• | Lack of lubricant on the O-rings |
• | Dirt/debris across an O-ring |
The smallest piece of lint from the following items may create a leak
path along an O-ring:
The successful use of this and any other electronic leak detector depends
greatly upon the following conditions:
• | Carefully following the manufacturer's instructions regarding
the following procedures: |
Completely circle each joint moving at 25 to 50 mm
(1 to 2 inches) per second. Ensure that the tip on the
probe is as close to the surface as possible but no more than 6 mm
(1/4 inch) away and without blocking the air intake. A leak is indicated
when the audible tone goes from a steady 1 to 2 clicks
per second to a solid alarm. Adjust the balance knob frequently in order
to maintain the 1 to 2 clicks per second rate.
Important: Halogen leak detectors are sensitive to the following items used in
the vehicle:
• | Windshield washing solutions |
• | Many solvents and cleaners |
Use care in order to prevent a false warning by ensuring that the surfaces
are clean. Ensure that the surfaces are dry since the ingestion of liquids
damages the detector. In order to ensure that no gasses are present that
may cause a false warning, blow out the engine compartment using an air
hose prior to the test.
Test the following areas using this procedure:
• | The pressure sensor (transducer) |
• | The evaporator inlet and outlet |
• | All the brazed and welded areas |
• | Areas showing signs of damage |
• | The compressor rear head and housing joints |
Important: Always follow the refrigerant system around in a continuous path in
order to ensure that no areas of potential leaks are missed. Always test all
of the above areas in order to ensure that the entire system is leak-free,
even when one leak is already found.
Service Access Ports
The primary seal for the service port is the sealing cap. This cap contains
a specially designed O-ring or gasket that provides a leak-free seal. A loss
of refrigerant charge may result under the following conditions:
The high side port is identified with a red cap. The low side port is
identified with a blue cap.
Evaporator Core
One of the most difficult leaks to find is in the evaporator core. The
core is encapsulated into a closed module. The core is inaccessible to leak
detector devices. Use the following procedure in order to test the core:
- Turn the blower fan on HIGH for 15 seconds. Shut the fan
off.
- Wait 10 minutes.
- Remove the blower motor or the blower resistor.
- Insert the leak detector probe into the opening. The detector
going to a solid alarm is an indication that there is a leak.
- If possible, use a flashlight in order to visually inspect the
core face for evidence of refrigerant oil.
Compressor and Block Fitting
A defective or a worn-out shaft seal often causes compressor gas leaks.
A small amount of compressor oil leakage from the shaft seal is normal. Replace
the compressor only when a large leak is detected. At times, an oil leak
can be detected visually. A gas leak check will require a gas leak detector.
- Blow shop air in the following locations for at least 15 seconds:
• | Behind the compressor clutch/pulley |
• | In front of the compressor clutch/pulley |
- Probe the compressor area. If the detector goes to a solid alarm,
a leak is present.
Fluorescent Leak Detection Method
Tools Required
• | J 41459 R134a
A/C Tracer Dye Injector |
• | J 42220 Universal 12 V Leak Detection Lamp |
Notice: The tracer dye J 41447 was developed for use with the A/C Refrigerant
134a (R-134a) equipped vehicles or with vehicles that have been retrofitted
from R-12 to R-134a. Do not use any other tracer dye in the R-134a system.
Use of another dye may affect the system reliability and cause premature compressor
failure. Use only a 1/4 oz. charge of the dye. Larger amounts may compromise
the reliability of the A/C system. After adding the tracer dye, clean the
service valves and all affected surfaces of the dye with GM Engine Degreaser
GM P/N 1050436 or an equivalent in order to prevent a false
diagnosis.
The R-134a refrigerant is uniquely different from the R-12
used in the past and may require additional methods for leak detection. The
R-134a molecule is smaller than the R-12 molecule and can leak through
smaller openings. R-134a also does not contain chlorine which was
easily detected using the black light. The fluorescent leak detection
method is meant to be used in conjunction with the electronic method,
and will pinpoint smaller leaks. The R-134a dye takes time to work
through the A/C system. Depending on the rate of the leak, the dye
may take up to 7 days to become visible.