The instrument panel integration module (IPM) monitors the air temperature in the left A/C duct via a temperature sensor. When the air is cold, the sensor resistance and signal voltage are high. When the air is warm, the sensor resistance and signal voltage are low. The IPM requests A/C clutch engagement and controls the left air mix door position in order to maintain the temperature selected on the driver temperature control.
The ignition is turned ON.
The IPM detects the signal circuit is less than 0.09 V (5 counts) or greater than 4.90 V (250 counts).
• | When outside air temperature (OAT) is at or below 15°C (59°F), a default value of 4.80 V (245 counts) will be used by the IPM. The temperature displayed on the scan tool, 31°C (23°F) in the HVAC Sensors data list, will be the default value. The actual sensor reading will be displayed on the scan tool in the Open/Short data list. |
• | When OAT is at or above 16°C (60°F), a default value of 0.19 V (10 counts) will be used by the IPM. The temperature displayed on the scan tool, 119°C (246°F) in the HVAC Sensors data list, will be the default value. The actual sensor reading will be displayed on the scan tool in the Open/Short data list. |
• | The DTC will become history if the IPM no longer detects a failure. |
• | The history DTC will clear after 50 fault free ignition cycles. |
• | The DTC can be cleared with a scan tool. |
The numbers below refer to the step numbers on the diagnostic table.
Tests for the proper operation of the circuit in the high voltage range.
Tests for the proper operation of the circuit in the low voltage range. If the fuse in the jumper opens when you perform this test, the signal circuit is shorted to voltage.
Step | Action | Values | Yes | No |
---|---|---|---|---|
1 | Did you perform the HVAC Diagnostic System Check? | -- | Go to Step 2 | Go to Diagnostic System Check |
2 |
Does the scan tool indicate that the Left AC Duct Temp parameter is within the specified range? | 0.09-4.90 V | Go to Testing for Intermittent Conditions and Poor Connections | Go to Step 3 |
Does the scan tool indicate that the Left AC Duct Temp parameter is greater than the specified value? | 4.90 V | Go to Step 4 | Go to Step 5 | |
Does the scan tool indicate that the Left A/C Duct Temp parameter is less than the specified value? | 0.09 V | Go to Step 8 | Go to Step 6 | |
5 | Test the signal circuit of the left panel discharge sensor for a short to ground. Refer to Circuit Testing and Wiring Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 12 | Go to Step 9 |
6 | Test the signal circuit of the left panel discharge sensor for a short to voltage, a high resistance, or an open. Refer to Circuit Testing and Wiring Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 12 | Go to Step 7 |
7 | Test the ground circuit of the left panel discharge sensor for a high resistance or an open. Refer to Circuit Testing and Wiring Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 12 | Go to Step 9 |
8 | Inspect for poor connections at the harness connector of the left panel discharge sensor. Refer to Testing for Intermittent Conditions and Poor Connections and Connector Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 12 | Go to Step 10 |
9 | Inspect for poor connections at the harness connector of the IPM. Refer to Testing for Intermittent Conditions and Poor Connections and Connector Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 12 | Go to Step 11 |
10 | Replace the left panel discharge sensor. Refer to Panel Discharge Sensor Replacement - Left Side . Did you complete the replacement? | -- | Go to Step 12 | -- |
11 | Replace the IPM. Refer to Instrument Panel Module Replacement in Body Control System. Did you complete the replacement? | -- | Go to Step 12 | -- |
12 |
Does the DTC reset? | -- | Go to Step 2 | System OK |