The EEPROM check sum error detection is handled inside the control module. No external circuits are involved.
The microprocessor runs the program in order to detect a check sum error after each "power up". The only requirements are voltage and ground. This program runs even if the voltage is out of the valid operating range.
The microprocessor reverts to base operation values programed for those blocks of data that have failed the check sum test. The blocks of data that have not failed the check sum test are not affected.
The DTC clears when the microprocessor runs a successful check sum test of the EEPROM.
Important: The DIM must be replaced if the DTC is retrieved as a current or a history DTC.
Important: The IPM must be recalibrated with the latest calibration before replacement. Refer to Instrument Panel Module Recalibration in HVAC - Automatic.
• | This DTC may be stored as a history DTC with out affecting the operation of the module. If stored only as a history DTC and not retrieved as a current DTC, do not replace the module. |
• | If this DTC is retrieved as both a current and history DTC, replace the module. |
Step | Action | Value(s) | Yes | No |
---|---|---|---|---|
1 | Did you perform the Diagnostic System Check? | -- | Go to Step 2 | |
2 | Is the module the instrument panel module (IPM)? | -- | Go to Step 3 | Go to Step 4 |
3 |
Is the DTC current? | -- | Go to Step 4 | System OK |
4 | Replace the module. Refer to Control Module References . Did you complete the replacement? | -- | System OK | -- |