Step | Action | Yes | No | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Schematic Reference: HVAC Schematics Connector End View Reference: HVAC Connector End Views DEFINITION: Air does not flow correctly from the air distribution outlets. | |||||||||||||||||
1 | Did you perform the HVAC Diagnostic System Check? | Go to Step 2 | |||||||||||||||
2 |
Is the blower motor OFF? | Go to Step 3 | Go to Blower Motor Always On | ||||||||||||||
3 | Place the blower motor switch in each speed position. Does the blower motor operate in any of the speed positions? | Go to Step 4 | Go to Blower Motor Inoperative | ||||||||||||||
4 | Does the blower motor operate in each speed position? | Go to Step 5 | Go to Blower Motor Malfunction | ||||||||||||||
5 |
Does the recirculation door move from the recirculation position to the ambient air position? | Go to Step 6 | |||||||||||||||
6 |
Does the air flow from the proper air distribution outlet in each mode position? | Go to Testing for Intermittent Conditions and Poor Connections in Wiring Systems | Go to Step 7 | ||||||||||||||
7 | Inspect the air delivery system for the following conditions:
Did you find and correct the condition? | Go to Step 18 | Go to Step 8 | ||||||||||||||
8 | Inspect the mode door and the mode actuator for the following conditions:
Did you find and correct the condition? | Go to Step 18 | Go to Step 9 | ||||||||||||||
9 |
Does the test lamp illuminate? | Go to Step 10 | Go to Step 15 | ||||||||||||||
10 | Test the low reference circuit of the mode actuator for an open or high resistance. Refer to Circuit Testing and Wiring Repairs in Wiring Systems. Did you find and correct the condition? | Go to Step 18 | Go to Step 11 | ||||||||||||||
11 |
Does the measured voltage change for each change in selected mode position? | Go to Step 13 | Go to Step 12 | ||||||||||||||
12 | Test the mode door control circuit of the mode actuator for an open, a high resistance, a short to ground, or a short to voltage. Refer to Circuit Testing and Wiring Repairs in Wiring Systems. Did you find and correct the condition? | Go to Step 18 | Go to Step 14 | ||||||||||||||
13 | Inspect for poor connections at the harness connector of the mode actuator. Refer to Testing for Intermittent Conditions and Poor Connections and Connector Repairs in Wiring Systems. Did you find and correct the condition? | Go to Step 18 | Go to Step 16 | ||||||||||||||
14 | Inspect for poor connections at the harness connector of the HVAC control module. Refer to Testing for Intermittent Conditions and Poor Connections and Connector Repairs in Wiring Systems. Did you find and correct the condition? | Go to Step 18 | Go to Step 17 | ||||||||||||||
15 | Repair the ignition 3 voltage circuit of the mode actuator. Refer to Wiring Repairs in Wiring Systems. Did you complete the repair? | Go to Step 18 | -- | ||||||||||||||
16 |
Important: Perform the recalibration procedure for the mode actuator. Replace the mode actuator. Refer to Mode Actuator Replacement . Did you complete the replacement? | Go to Step 18 | -- | ||||||||||||||
17 | Replace the HVAC control module. Refer to HVAC Control Module Replacement . Did you complete the replacement? | Go to Step 18 | -- | ||||||||||||||
18 | Operate the system in order to verify the repair. Did you correct the condition? | System OK | Go to Step 7 |