Table 1: | A/C Performance Table |
This test measures the operating efficiency of the A/C system under the following conditions:
• | The current ambient air temperature |
• | The current relative humidity |
• | The high side pressure of the A/C system |
• | The low side pressure of the A/C system |
• | The temperature of the air being discharged into the passenger compartment |
The numbers below refer to the step numbers on the diagnostic table.
This step determines if the A/C system has at least the minimum refrigerant charge required to operate the system without damage.
This step measures the performance of the A/C system.
This step is to allow for vehicle variations as well as high ambient temperatures.
Step | Action | Values | Yes | No | ||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Important:
| ||||||||||||||||||||||||||||||||||||||||
Are both the low side and high side pressures within the specified value? | More than 16°C (60°F) - 345 kPa (50 psi) More than 24°C (75°F) - 483 kPa (70 psi) More than 33°C (90°F) - 690 kPa (100 psi) | Go to Step 2 | Go to Leak Testing | |||||||||||||||||||||||||||||||||||||
Important: Record the relative humidity and the ambient air temperature at the time of the test.
Important: Press the RESET button, before using the print function of the J 43600 .
Does all the data recorded fall within the specified ranges of the A/C performance table? | -- | Go to Step 8 | Go to Step 3 | |||||||||||||||||||||||||||||||||||||
If the pressures and temperatures recorded do not fall within the specified ranges:
Does all the data recorded fall within the specified ranges of the A/C performance table? | -- | Go to Step 8 | Go to Step 4 | |||||||||||||||||||||||||||||||||||||
4 | Do the high and low side pressures fall within the specified ranges, but the panel outlet temperatures do not? | -- | Go to Step 5 | |||||||||||||||||||||||||||||||||||||
5 | Is the low side pressure greater than the specified range, but the high side pressure within or less than the specified range? | -- | Go to Step 6 | |||||||||||||||||||||||||||||||||||||
6 | Are the low and high side pressures both greater than the specified ranges? | -- | Go to Step 7 | |||||||||||||||||||||||||||||||||||||
7 | Is the high side pressure greater than the specified range, but the low side pressure is within or less than the specified range? | -- | Go to Step 8 | |||||||||||||||||||||||||||||||||||||
8 | Operate the system in order to verify the test results. Did you find the same results? | -- | System OK | Go to Symptoms - HVAC Systems - Manual or Symptoms - HVAC Systems - Automatic |
Ambient Air Temperature | Relative Humidity | Service Port Pressure | Maximum Left Center Discharge Air Temperature | |
---|---|---|---|---|
Low Side | High Side | |||
16-20°C (60-69°F) | 0-100% | 193-234 kPa (28-34 psi) | 896-1103 kPa (130-160 psi) | 9°C (49°F) |
21-26°C (70-79°F) | Below 40% | 221-262 kPa (32-38 psi) | 1103-1310 kPa (160-190 psi) | 11°C (52°F) |
Above 40% | 234-276 kPa (34-40 psi) | 1207-1413 kPa (175-205 psi) | 11°C (52°F) | |
27-31°C (80-89°F) | Below 40% | 172-214 kPa (25-31 psi) | 1020-1227 kPa (148-178 psi) | 13°C (55°F) |
Above 40% | 296-331 kPa (43-48 psi) | 1207-1413 kPa (175-205 psi) | 14°C (58°F) | |
32-37°C (90-99°F) | Below 30% | 262-303 kPa (38-44 psi) | 1241-1448 kPa (180-210 psi) | 12°C (53°F) |
Above 30% | 283-324 kPa (41-47 psi) | 1241-1448 kPa (180-210 psi) | 16°C (60°F) | |
38-42°C (100-109°F) | Below 30% | 317-379 kPa (46-56 psi) | 1413-1689 kPa (205-245 psi) | 16°C (63°F) |
Above 30% | 317-379 kPa (46-56 psi) | 1448-1724 kPa (210-250 psi) | 18°C (65°F) | |
43-48°C (110-119°F) | Below 25% | 331-400 kPa (48-58 psi) | 1655-1931 kPa (240-280 psi) | 17°C (63°F) |
Above 25% | 352-421 kPa (51-61 psi) | 1655-1931 kPa (240-280 psi) | 22°C (71°F) | |
Above 49°C (120°F) | Below 30% | 400-469 kPa (58-68 psi) | 1896-2172 kPa (275-315 psi) | 23°C (73°F) |