The internal fault detection is handled inside the control module. No external circuits are involved.
The microprocessor runs the program to detect an internal fault when power up is commanded. The only requirements are voltage and ground. This program runs even if the voltage is out of the valid operating range.
The microprocessor refuses all additional inputs.
The DTC clears when the microprocessor makes a successful write to the RAM.
• | This DTC may be stored as a history DTC with out affecting the operation of the module. If stored only as a history DTC and not retrieved as a current DTC, do not replace the module. |
• | If this DTC is retrieved as both a current and history DTC, replace the module. |
Step | Action | Yes | No |
---|---|---|---|
1 | Did you perform the Instrument Cluster Diagnostic System Check? | Go to Step 2 | |
2 | Replace the IPC. Refer to Instrument Cluster Replacement . Did you complete the replacement? | Go to Step 3 | -- |
3 |
Does the DTC reset? | Go to Step 1 | System OK |