Step
| Action
| Value(s)
| Yes
| No
|
1
|
- Disconnect the blower motor resistor connector.
- Turn the ignition switch to the ON position.
- Place the heater-A/C control in the VENT position.
- Place the blower switch to the inoperative position.
- Using a test light, backprobe between ground and the blower motor
resistor connector terminal listed below:
Does the test light illuminate?
| --
| Go to
Step
2
| Go to
Step
3
|
2
| Replace the blower motor resistor. Refer to
Blower Motor Resistor Replacement
.
Is the repair complete?
| --
| Go to
HVAC Air Delivery System Check
| --
|
3
|
- Turn the ignition switch to the OFF position.
- Disconnect the HVAC control assembly connector C1.
- Inspect for a poor connection, an open or a short to ground in
the inoperative circuit listed below:
Is there a poor connector, an open, or a short to ground in the inoperative
circuit tested?
| --
| Go to
Step 4
| Go to
Step 5
|
4
| Locate and repair the fault in the circuit.
Is the repair complete?
| --
| Go to
HVAC Air Delivery System Check
| --
|
5
| Replace the HVAC control assembly. Refer to
Control Assembly Replacement
.
Is the repair complete?
| --
| Go to
HVAC Air Delivery System Check
| --
|