The numbers below refer to the step numbers on the diagnostic table.
Step | Action | Value | Yes | No | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Schematic Reference: HVAC Schematics Connector End View Reference: HVAC Connector End Views DEFINITION: Air does not flow correctly from the air distribution outlets. | ||||||||||||||||
1 | Did you perform the HVAC Diagnostic System Check? | -- | Go to Step 2 | |||||||||||||
2 |
Is the blower motor OFF? | -- | Go to Step 3 | Go to Blower Motor Always On | ||||||||||||
3 | Place the blower motor switch in each speed position. Does the blower motor operate in any speed position? | -- | Go to Step 4 | Go to Blower Motor Inoperative | ||||||||||||
4 | Does the blower motor operate in each speed position? | -- | Go to Step 5 | Go to Blower Motor Malfunction | ||||||||||||
5 | Are all of the HVAC control module controls except for the blower motor inoperative? | -- | Go to Step 14 | Go to Step 6 | ||||||||||||
6 |
Does the recirculation door move from the recirculation to the outside air position? | -- | Go to Step 7 | |||||||||||||
7 |
Does air flow sufficiently from the proper air distribution outlets for each selected mode position? | -- | Go to Testing for Intermittent Conditions and Poor Connections in Wiring Systems | Go to Step 8 | ||||||||||||
8 | Inspect the air delivery system for the following conditions:
Did you find and correct the condition? | -- | Go to Step 23 | Go to Step 9 | ||||||||||||
9 | Inspect the mode door and the mode actuator for the following conditions:
Did you find and correct the condition? | -- | Go to Step 23 | Go to Step 10 | ||||||||||||
10 |
Does the test lamp illuminate? | -- | Go to Step 11 | Go to Step 20 | ||||||||||||
11 | Test the ground circuit of the mode actuator for an open or for a high resistance. Refer to Circuit Testing and to Wiring Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 23 | Go to Step 12 | ||||||||||||
Does the voltage measure near the specified values for each mode position? | Vent: 0.2V, Bi-Level: 3.1V, Floor: 5.0V Mix-Blend: 8.9V, Defrost: 11.8V | Go to Step 18 | Go to Step 13 | |||||||||||||
13 | Test the mode door control circuit of the mode actuator for an open, a high resistance, a short to ground, or a short to voltage. Refer to Circuit Testing and to Wiring Repairs in Wiring Systems. Did you find and correct the condition? | --- | Go to Step 23 | Go to Step 19 | ||||||||||||
Test the ignition 3 voltage circuit of the HVAC control module for an open or for a high resistance. Refer to Circuit Testing and to Wiring Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 23 | Go to Step 15 | |||||||||||||
15 | Test the battery positive voltage circuit of the HVAC control module for an open or for a high resistance. Refer to Circuit Testing and to Wiring Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 23 | Go to Step 16 | ||||||||||||
16 | Test the ground circuit of the HVAC control module for an open or for a high resistance. Refer to Circuit Testing and to Wiring Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 23 | Go to Step 17 | ||||||||||||
17 | Test the off blower motor control circuit of the HVAC control module for a short to voltage. Refer to Circuit Testing and to Wiring Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 23 | Go to Step 19 | ||||||||||||
18 | Inspect for bad connections at the harness connector of the mode actuator. Refer to Testing for Intermittent Conditions and Poor Connections and to Connector Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 23 | Go to Step 21 | ||||||||||||
19 | Inspect for bad connections at the harness connector of the HVAC control module. Refer to Testing for Intermittent Conditions and Poor Connections and to Connector Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 23 | Go to Step 22 | ||||||||||||
20 | Repair the ignition 3 voltage circuit of the mode actuator. Refer to Wiring Repairs in Wiring Systems. Did you complete the repair? | -- | Go to Step 23 | -- | ||||||||||||
21 | Replace the mode actuator. Refer to Mode Actuator Replacement . Did you complete the replacement? | -- | Go to Step 23 | -- | ||||||||||||
22 | Replace the HVAC Control module. Refer to HVAC Control Module Replacement . Did you complete the replacement? | -- | Go to Step 23 | -- | ||||||||||||
23 | Operate the system in order to verify the repair. Did you correct the condition? | -- | System OK | Go to Step 8 |