The number below refers to the step number on the diagnostic table.
Step | Action | Value(s) | Yes | No | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Schematic Reference: HVAC Schematics Connector End View Reference: HVAC Connector End Views DEFINITION: Air does not flow correctly from the air distribution outlets. | ||||||||||||||
1 | Did you perform the HVAC Diagnostic System Check? | -- | Go to Step 2 | |||||||||||
2 |
Is the blower motor OFF? | -- | Go to Step 3 | Go to Blower Motor Always On | ||||||||||
3 | Place the blower motor switch in each speed position. Does the blower motor operate at all? | -- | Go to Step 4 | Go to Blower Motor Inoperative | ||||||||||
4 | Does the blower motor operate in each speed position? | -- | Go to Step 5 | Go to Blower Motor Malfunction | ||||||||||
5 | Place the recirculation switch in the recirculation and outside air positions. Does the recirculation actuator move from the recirculation position to the outside air position? | -- | Go to Step 6 | |||||||||||
6 | Place the mode switch in each position. Is the air flow sufficient from the correct outlets in each mode? | -- | Go to Testing for Intermittent Conditions and Poor Connections in Wiring Systems | Go to Step 7 | ||||||||||
7 |
Does the test lamp illuminate? | -- | Go to Step 8 | Go to Step 17 | ||||||||||
8 | Measure the voltage from the 5-volt reference circuit of the mode actuator to a good ground. Does the voltage measure near the specified value? | 5 V | Go to Step 9 | Go to Step 13 | ||||||||||
9 | Test the mode door control circuit of the mode actuator for an open, short to ground or short to voltage. Refer to Circuit Testing and Wiring Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 20 | Go to Step 10 | ||||||||||
10 | Test the mode door signal circuit for a short to ground. Refer to Circuit Testing and Wiring Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 20 | Go to Step 11 | ||||||||||
Does the voltage measure near the specified value for each commanded state? | 0.1 V DEFROST 4.95 V A/C | Go to Step 14 | Go to Step 12 | |||||||||||
12 |
Does the result of your calculation indicate that the door travel range is greater than the specified value? | 200 Counts | Go to Step 16 | Go to Step 14 | ||||||||||
13 | Test the 5-volt reference circuit of the mode actuator for an open. Refer to Circuit Testing and Wiring Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 20 | Go to Step 16 | ||||||||||
14 | Inspect the mode door and the mode actuator for the following conditions:
Did you find and correct the condition? | -- | Go to Step 20 | Go to Step 15 | ||||||||||
15 | Inspect for poor connections at the harness connector of the mode actuator. Refer to Testing for Intermittent Conditions and Poor Connections and Connector Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 20 | Go to Step 18 | ||||||||||
16 | Inspect for poor connections at the harness connector of the IPM. Refer to Testing for Intermittent Conditions and Poor Connections and Connector Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 20 | Go to Step 19 | ||||||||||
17 | Repair the ignition 3 voltage circuit of the mode actuator. Refer to Wiring Repairs in Wiring Systems. Did you complete the repair? | -- | Go to Step 20 | -- | ||||||||||
18 |
Important: Perform the recalibration procedure for the mode actuator. Replace the mode actuator. Refer to Mode Actuator Replacement . Did you complete the replacement? | -- | Go to Step 20 | -- | ||||||||||
19 |
Important: Perform the recalibration procedure for the IPM. Replace the IPM. Refer to HVAC Control Module Replacement . Did you complete the replacement? | -- | Go to Step 20 | -- | ||||||||||
20 | Operate the system in order to verify the repair. Did you correct the condition? | -- | System OK | Go to Step 2 |