Step | Action | Value(s) | Yes | No | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
1 | Test the cooling system for the following conditions:
Repair the cooling system as necessary. Is the repair complete? | -- | Go to Step 2 | -- | ||||||||||
2 |
Is the airflow high? | -- | Go to Step 3 | Go to Step 11 | ||||||||||
3 | Check the blower speeds for changes in the airflow . Do the blower speeds change? | -- | Go to Step 4 | Go to Step19 | ||||||||||
4 | Perform the heater output temperature check. Is the heater output temperature low? | -- | Go to Step 20 | Go to Step 5 | ||||||||||
5 | Close the temperature valve. Is the temperature valve closed? | -- | Go to Step 6 | -- | ||||||||||
6 | Turn the temperature rotary knob to full HOT. Is the temperature valve fully closed? | -- | Go to Step 7 | Go to Step 25 | ||||||||||
7 |
Is the air temperature around both hoses equal to or greater than the specified value? | 85°F (24°C) | Go to Step 8 | Go to Step 27 | ||||||||||
8 |
Are the hoses properly installed? | -- | Go to Step 9 | Go to Step 24 | ||||||||||
9 |
Are both hoses warm? | -- | Go to Step 10 | Go to Step 26 | ||||||||||
10 | Replace the heater core. Refer to Heater Core Replacement . Is the repair complete? | -- | -- | |||||||||||
11 | Perform the functional test. Refer to Function Test . Did you find and correct the condition? | -- | Go to Step 12 | |||||||||||
12 | Check the air flow from the defroster and vent outlets. Is the airflow high? | -- | Go to Step 21 | Go to Step 13 | ||||||||||
13 |
Is the air flow high? | -- | -- | Go to Step 14 | ||||||||||
14 | Check the blower speeds for airflow change. Do the speeds change? | -- | Go to Step 15 | -- | ||||||||||
15 | Inspect the blower at the blower inlet and the plenum for airflow obstructions. Are the blower inlet and the plenum free of obstructions? | -- | Go to Step 16 | -- | ||||||||||
16 |
Did the airflow change? | -- | Go to Step 17 | Go to Step 18 | ||||||||||
17 | Inspect the system for airflow obstructions between the blower and the system outlets. Did you find and remove any obstructions? | -- | -- | |||||||||||
18 | Inspect the following components:
Did you find and repair a condition? | -- | -- | |||||||||||
19 |
Is the procedure complete? | -- | Go to Step 5 | -- | ||||||||||
20 |
Are the components clear of obstructions? | -- | -- | |||||||||||
21 | Move the defroster and/or vent valve to the HEATER mode. Is the defroster airflow correct? | -- | Go to Step 22 | -- | ||||||||||
22 |
Does the air speed remain constant? | -- | Go to Step 23 | Go to Step 15 | ||||||||||
23 |
Is the repair complete? | -- | Go to Step 6 | -- | ||||||||||
24 | Properly install the hoses. Is the installation complete? | -- | Go to Step 1 | -- | ||||||||||
25 |
Is the repair complete? | -- | -- | |||||||||||
26 |
Is the repair complete? | -- | -- | |||||||||||
27 |
Are the installation and seating correct? | -- | Go to Step 28 | Go to Step 29 | ||||||||||
28 | Replace the thermostat. Is the repair complete? | -- | -- | |||||||||||
29 |
Is the repair complete? | -- | -- |