2.1. | Simultaneously press RESET (7) and ENTER (5). |
2.2. | Press 6. |
2.3. | If the display reads less than 16 kg (36 lb), add refrigerant to the tank. Refer to the manufacturer's instructions. |
Important: In order to properly remove all of the air and dry the A/C system, the unit automatically goes to a pre-programmed evacuation cycle.
• | The display counts down the vacuum time to zero (0) in order to indicate the time remaining. |
• | The display reads RECYCLE five seconds after the vacuum pump starts and continues while the process takes place. |
• | Automatic refrigerant recycling during each evacuation is a feature of the ACR4 system. No action is required by the technician. |
• | The control panel MOISTURE indicator (5) must be green during recycling in order to verify that the moisture content is within specifications. Yellow indicates a set condition requiring a filter/drier cartridge change. See the manufacturer instructions for this procedure. |
• | Noncondensable gases (mostly air) are automatically vented from the tank during the recycling process. An audible sound of pressure release may be heard as this happens and is a normal function. |
• | (0) reading: |
- | Inspect for a major system leak. Refer to Leak Testing . |
- | Repair the leak before resuming this procedure. |
• | 91-101 kPa (27-30 in Hg) indicated: |
- | Close the high (4) and low (6) side valves. |
- | Observe the vacuum level. |
- | If a 91-101 kPa (27-30 in Hg) vacuum is not maintained, diagnose the A/C system for a leak before resuming the evacuation procedure. Refer to Leak Testing . |
- | After a 91-101 kPa (27-30 in Hg) is maintained, open the high and low side valves. |