Step | Action | Yes | No | ||||||
---|---|---|---|---|---|---|---|---|---|
DEFINITION: The low and the high side pressures are both higher than normal.
Tools RequiredJ 43600 ACR 2000 | |||||||||
1 | Were you sent here from the A/C System Performance Test? | Go to Step 2 | |||||||
2 |
Are the cooling fans ON and operating properly? | Go to Step 3 | Go to Step 5 | ||||||
3 | Visually inspect for the following conditions:
Do any of these conditions exist? | Go to Step 4 | Go to Step 6 | ||||||
4 | Repair the air flow restriction. Is the action complete? | Go to Step 9 | -- | ||||||
5 | Repair the fault to the cooling fan operation. Refer to Cooling Fan Inoperative in Engine Cooling. Is the action complete? | Go to Step 9 | -- | ||||||
6 |
Caution: Refer to Moving Parts and Hot Surfaces Caution in the Preface section. Feel the liquid line on both sides of the expansion device. Are the temperatures on both sides of the expansion device similar? | Go to Step 7 | Go to Step 8 | ||||||
7 | Replace the damaged or faulty orifice tube. Refer to Expansion (Orifice) Tube Replacement . Is the action complete? | Go to Step 9 | -- | ||||||
8 |
Is the action complete? | Go to Step 9 | -- | ||||||
9 |
Are the readings within the specified ranges listed in the A/C Performance Chart? | Go to Step 10 | |||||||
10 | Operate the system in order to verify the repair. Did you find and correct the condition? | System OK | Go to Symptoms - HVAC Systems - Automatic in HVAC systems - Automatic. |