Step  | Action  | Yes  | No  | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
DEFINITION: Noise originating from the HVAC module.  | |||||||||||||||
1  | Were you sent here from Symptoms or another diagnostic table?  | Go to Step 2  | Go to Symptoms - HVAC Systems - Manual or  | ||||||||||||
2  | 
 
 
 
 
 
 
 Is noise evident when selecting recirculation?  | Go to Step 6  | Go to Step 3  | ||||||||||||
3  | Is noise evident when selecting temperature?  | Go to Step 6  | Go to Step 4  | ||||||||||||
4  | Is noise evident when selecting mode ?  | Go to Step 5  | Go to Step 2  | ||||||||||||
5  | 
 Is dust, dirt or debris present?  | Go to Step 11  | Go to Step 12  | ||||||||||||
6  | Remove the HVAC module. Refer to HVAC Module Assembly Replacement . Is action complete?  | Go to Step 7  | --  | ||||||||||||
7  | 
 Were any of these conditions found?  | Go to Step 10  | Go to Step 8  | ||||||||||||
8  | Inspect air flow door for warping or cracking. Is air flow door in normal condition?  | Go to Step 13  | Go to Step 9  | ||||||||||||
9  | Replace air flow door . Is repair complete?  | Go to Step 13  | --  | ||||||||||||
10  | Remove any obstructions or foreign material found. Is action complete?  | Go to Step 13  | --  | ||||||||||||
11  | Vacuum and remove dust, dirt and debris. Is action complete?  | Go to Step 14  | --  | ||||||||||||
12  | Replace the upper evaporator case. Refer to Air Conditioning Evaporator Core Replacement . Is action complete?  | Go to Step 14  | --  | ||||||||||||
13  | Install HVAC Module. Refer to HVAC Module Assembly Replacement . Is action complete?  | Go to Step 14  | --  | ||||||||||||
14  | Operate the system to verify the repair. Did you find and correct the condition?  | System OK  | Go to Step 2  | ||||||||||||