Step | Action | Values | Yes | No |
---|---|---|---|---|
Schematic Reference: HVAC Schematics | ||||
1 | Measure the voltage between terminal 4 and terminal 5 of the mode motor. Is the voltage measured within the specified range? | 11-14 V | Go to Step 3 | Go to Step 2 |
2 |
Did you find and correct the condition? | -- | System OK | Go to Step 3 |
3 |
Are the voltages measured as specified in the Motor Control Table? | -- | Go to Step 4 | Go to Step 5 |
4 | Replace the motor that does not operate properly. Did you complete the replacement? | -- | System OK | -- |
5 |
Are the voltages measured as specified in the Motor Control Table? | -- | Go to Step 6 | Go to Step 7 |
6 |
Did you find and correct the condition? | -- | System OK | -- |
7 | Inspect the connector at the controller. Is there a defective terminal? | -- | Go to Step 8 | Go to Step 9 |
8 | Repair or replace the terminal. Did you find and correct the condition? | -- | System OK | -- |
9 | Replace the controller. Did you complete the replacement? | -- | System OK | -- |