Step | Action | Yes | No | ||||
---|---|---|---|---|---|---|---|
Schematic Reference: HVAC Schematics | |||||||
1 | Did you review the Air Delivery Description and Operation and the Air Temperature Description and Operation and perform the necessary inspections? | Go to Step 2 | |||||
2 |
Does the condenser fan motor operate? | Go to Testing for Intermittent Conditions and Poor Connections in Wiring Systems | Go to Step 3 | ||||
3 | Connect a scan tool and command the condenser fan relay ON. If the relay energizes, the malfunction is in the fan motor, the wiring between the motor and G105 or high resistance in the relay contacts. If the relay does not energize, the malfunction is in the relay, the PCM, or the relay control wiring. Does the condenser fan relay energize? | Go to Step 4 | Go to Step 8 | ||||
4 |
Does the test lamp illuminate? | Go to Step 12 | Go to Step 5 | ||||
5 | Test the condenser fan ground circuit for an open. Refer to Circuit Testing and Wiring Repairs in Wiring Systems. Did you find and correct the condition? | Go to Step 17 | Go to Step 6 | ||||
6 | Test the condenser fan supply voltage circuit for an open. Refer to Circuit Testing and Wiring Repairs in Wiring Systems. Did you find and correct the condition? | Go to Step 17 | Go to Step 7 | ||||
7 | Test the condenser fan relay switch supply voltage circuit for an open. Refer to Circuit Testing and Wiring Repairs in Wiring Systems. Did you find and correct the condition? | Go to Step 17 | -- | ||||
8 | Test the condenser fan relay for an open in the coil between terminals 1 and 3. Is the condenser fan relay coil open? | Go to Step 15 | Go to Step 9 | ||||
9 | Test the condenser fan relay coil supply voltage circuit for an open. Refer to Circuit Testing and Wiring Repairs in Wiring Systems. Did you find and correct the condition? | Go to Step 17 | Go to Step 10 | ||||
10 | Test the condenser fan relay control circuit for an open. Refer to Circuit Testing and Wiring Repairs in Wiring Systems. Did you find and correct the condition? | Go to Step 17 | Go to Step 11 | ||||
11 |
Does the test lamp illuminate? | -- | Go to Step 13 | ||||
12 | Inspect for a poor connection or for a high resistance at the harness connector of the condenser fan. Refer to Testing for Intermittent Conditions and Poor Connections and Connector Repairs in Wiring Systems. Did you find and correct the condition? | Go to Step 17 | Go to Step 14 | ||||
13 | Inspect for a poor connection or for a high resistance at the harness connector of the PCM. Refer to Testing for Intermittent Conditions and Poor Connections and Connector Repairs in Wiring Systems. Did you find and correct the condition? | Go to Step 17 | Go to Step 16 | ||||
14 | Replace the condenser fan. Refer to Condenser Fan Replacement . Did you complete the replacement? | Go to Step 17 | -- | ||||
15 | Replace the condenser fan relay. Refer to Condenser Fan Relay Replacement . Did you complete the replacement? | Go to Step 17 | -- | ||||
16 | Replace the PCM. Refer to the following:
Did you complete the replacement? | Go to Step 17 | -- | ||||
17 | Operate the system in order to verify the repair. Did you correct the condition? | System OK | Go to Step 3 |