Step | Action | Yes | No | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
DEFINITION: The low side pressure is lower than normal and the high side pressure is higher than normal.
| |||||||||||||||||
1 | Were you sent here from the A/C System Performance Test? | Go to Step 2 | |||||||||||||||
2 |
Caution: Refer to Moving Parts and Hot Surfaces Caution in the Preface section. Feel the liquid line before the expansion device. Is the liquid line cold before the expansion device? | Go to Step 3 | Go to Step 8 | ||||||||||||||
3 | Feel along the surfaces of the following high side components:
Did you detect an abrupt drop in temperature along the surfaces of any of the listed components? | Go to Step 7 | Go to Step 4 | ||||||||||||||
4 |
Is the liquid line extremely cold at the expansion device location and warm beyond the expansion device location? | Go to Step 11 | Go to Step 5 | ||||||||||||||
5 | Feel along the surfaces of the following low side components.
Did you feel an abrupt temperature change along the surfaces of any of the listed components? | Go to Step 7 | Go to Step 6 | ||||||||||||||
6 | Feel along the surfaces of the low and the high side components.
Are the temperatures of these components only mildly warm? | Go to Step 14 | Go to Step 8 | ||||||||||||||
7 |
Is the repair complete? | Go to Step 9 | -- | ||||||||||||||
8 |
Is the weight of the recovered refrigerant charge greater than 75 percent of the total system capacity? | Go to Step 9 | Go to Step 10 | ||||||||||||||
9 | Recharge the A/C system. Refer to Refrigerant Recovery and Recharging . Is the cooling performance improved? | Go to Step 21 | Go to Step 10 | ||||||||||||||
10 |
Is the repair complete? | Go to Step 21 | -- | ||||||||||||||
11 | The expansion device is restricted. Replace the expansion device. Refer to Expansion (Orifice) Tube Replacement . Are metal flakes present? | Go to Step 12 | Go to Step 13 | ||||||||||||||
12 |
Did a large amount of debris collect in the shop towel? | Go to Step 18 | Go to Step 20 | ||||||||||||||
13 | If the expansion device was restricted with a brown or black residue, perform the following procedure:
Are the repairs complete? | Go to Step 21 | -- | ||||||||||||||
14 |
Is debris present in the compressor suction port? | Go to Step 15 | Go to Step 19 | ||||||||||||||
15 |
Did you find evidence of damage or debris? | Go to Step 17 | Go to Step 16 | ||||||||||||||
16 | If the expansion device does not show any signs of damage or debris, perform the following procedure:
Did a large amount of debris collect in the shop towel? | Go to Step 18 | Go to Step 19 | ||||||||||||||
17 |
Are metal flakes present? | Go to Step 12 | Go to Step 13 | ||||||||||||||
18 | If a large amount of debris was collected in the shop towel from the compressor hose assembly, perform the following procedure: Replace the accumulator. Refer to Air Conditioning Accumulator Replacement . Is the repair complete? | Go to Step 19 | -- | ||||||||||||||
19 | Install the compressor hose assembly. Refer to Compressor Hose Assembly Replacement . Are the repairs complete? | Go to Step 21 | -- | ||||||||||||||
20 |
Are the repairs complete? | Go to Step 21 | -- | ||||||||||||||
21 |
Are the readings within the specified ranges as shown on the A/C Performance Chart? | Go to Step 22 | |||||||||||||||
22 | Operate the system in order to verify the repair. Did you find and correct the condition? | System OK | Go to Symptoms - HVAC Systems - Manual or |