A/C Pressure Sensor: The scan tool displays 0-3450
kPa (0-500 psi). The voltage applied to the PCM input from the A/C
refrigerant pressure sensor is converted to a pressure value.
A/C Pressure Sensor: The scan tool displays 0-5
volts. The voltage applied to the PCM input for the A/C refrigerant pressure
sensor.
A/C Switch: The scan tool displays On/Off. The scan
tool displays On when the A/C request switch is active. The scan tool displays
Off when the A/C request switch is inactive.
AC Permission: The scan tool displays Withheld/Granted.
The scan tool displays Granted when the HVAC control module determines that
conditions for compressor clutch engagement are present. The scan tool displays
Withheld when the HVAC control module determines that conditions for compressor
clutch engagement are not present.
A/C Relay Command: The scan tool displays On/Off. The
scan tool displays the control decision for the compressor clutch relay output
as determined by the PCM.
A/C Request Signal: The scan tool displays Yes/No. The
scan tool displays Yes when the PCM receives a class 2 message from
the HVAC control module to engage the A/C compressor clutch. The scan tool
displays No when the PCM receives a class 2 message from the HVAC
control module to disengage the A/C compressor clutch.
Air Inlet Commanded: The scan tool displays 0-255
counts. The scan tool displays the desired recirculation door position as
determined by the HVAC control module.
Air Inlet Door Actual: The scan tool displays 0-255
counts. The voltage applied to the recirculation door position input of the
HVAC control module is converted to a number between 0 and 255 where 51 Counts
is approximately equal to 1 V.
Air Inlet Drive Motor: The scan tool displays Stop,
Increase, or Decrease. The scan tool displays the control decision for the
actuator output as determined by the HVAC control module.
Air Mix Door Left Commanded: The scan tool displays
0-255 counts. The scan tool displays the desired left air temperature
door position as determined by the HVAC control module.
Air Mix Door Right Commanded: The scan tool displays
0-255 counts. The scan tool displays the desired right air temperature
door position as determined by the HVAC control module.
Auto Switch: The scan tool displays On/Off. The scan
tool displays On when the automatic switch is active. The scan tool displays
Off when the automatic switch is inactive.
Battery Voltage: The scan tool displays 0-25 volts.
The voltage measured from the battery positive voltage circuit and the ground
circuit of the HVAC control module.
Blower Motor PWM: The scan tool displays 0-114%.
The scan tool displays the control decision for the blower motor speed as
determined by the HVAC control module. The scan tool displays 114% when
the blower motor is commanded to maximum speed. The scan tool displays 0%
when the blower motor is commanded OFF.
Engine Coolant Temp: The scan tool displays -39 to
140°C (-38 to 284°F). The scan tool displays the engine coolant temperature
as detected by the PCM.
ECT Sensor: The scan tool displays -39 to 140°C
(-38 to 284°F) . The voltage applied to the PCM input from the engine
coolant temperature sensor is converted to a temperature value.
ECT Sensor: The scan tool displays 0-5 volts.
The voltage applied to the PCM input for the engine coolant temperature sensor.
Fan Down Button: The scan tool displays On/Off. The
scan tool displays On when the fan down switch is active. The scan tool displays
Off when the fan down switch is inactive.
Fan Up Button: The scan tool displays On/Off. The scan
tool displays On when the fan up switch is active. The scan tool displays
Off when the fan up switch is inactive.
Front Defrost Switch: The scan tool displays On/Off.
The scan tool displays On when the defrost switch is active. The scan tool
displays Off when the defrost switch is inactive.
Ign. Since Current DTC: The scan tool displays 0-100.
The number of the ignition cycles since the setting of the most recent current
diagnostic trouble code (DTC).
Inside Air Temp Fan: The scan tool displays On/Off.
The scan tool displays the control decision for the fan motor output as determined
by the HVAC control module. The fan motor is internal to the inside air
temperature sensor assembly.
Inside Air Temp.: The scan tool displays -40 to
215°C (-40 to 419°F). The voltage applied to the HVAC control module
input for the inside air temperature sensor is converted to a temperature
value.
Left Mix Door Actual: The scan tool displays 0-255
counts. The voltage applied to the left air temperature door position input
of the HVAC control module is converted to a number between 0 and 255 where
51 Counts is approximately equal to 1 V.
Left Mix Motor Drive: The scan tool displays Stop, Increase,
or Decrease. The scan tool displays the control decision for the actuator
output as determined by the HVAC control module.
Left Solar Sensor: The scan tool displays 0-255
counts. The voltage applied to the left sunload input of the BCM is converted
to a number between 0 and 255 where 51 Counts is approximately equal
to 1 V.
Left Temp. Setting: The scan tool displays 15 to 32°C
(60 to 90°F). The scan tool displays the selected temperature from the
left air temperature switch.
LH AC Duct Actual: The scan tool displays 0-255
counts. The voltage applied to the left upper duct air temperature input
of the HVAC control module is converted to a number between 0 and 255 where
51 Counts is approximately equal to 1 V.
LH AC Duct Desired: The scan tool displays 0-255
counts. The desired value of the left upper duct air temperature input.
The HVAC control module monitors the actual value of the duct air temperature
input and accordingly positions the left air temperature door to achieve
the desired duct air temperature.
LH Heater Duct Actual: The scan tool displays 0-255
counts. The voltage applied to the left lower duct air temperature input
of the HVAC control module is converted to a number between 0 and 255 where
51 Counts is approximately equal to 1 V.
LH Heater Duct Desired: The scan tool displays 0-255
counts. The desired value of the left lower duct air temperature input.
The HVAC control module monitors the actual value of the duct air temperature
input and accordingly positions the left air temperature door to achieve
the desired duct air temperature.
Mode Door Actual: The scan tool displays 0-255
Counts. The voltage applied to the HVAC control module input for the mode
door position is converted to a number between 0 and 255 where 51 Counts
is approximately equal to 1 V.
Mode Commanded: The scan tool displays 0-255 counts.
The scan tool displays the desired mode door position as determined by the
HVAC control module.
Mode Motor Drive: The scan tool displays Stop, Increase,
or Decrease. The scan tool displays the control decision for the actuator
output as determined by the HVAC control module.
Mode Select Position: The scan tool displays Off, Auto,
Defrost, Heater, Htr/Def, Bi-Level, Panel. The scan tool displays the state
of mode operation.
Mode Switch: The scan tool displays On/Off. The scan
tool displays On when the mode switch is active. The scan tool displays Off
when the mode switch is inactive.
Off Switch: The scan tool displays On/Off. The scan
tool displays On when the Off switch is active. The scan tool displays Off
when the Off switch is inactive.
Outside Air Temp. Filtered: The scan tool displays -40
to 215°C (-40 to 419°F). The current value of the ambient air temperature
display on the HVAC control module.
Outside Air Temp. Raw: The scan tool displays -40
to 215°C (-40 to 419°F). The voltage applied to the HVAC control
module input from the ambient air temperature sensor is converted to an
unfiltered temperature value.
Pressure Cycle Switch: The scan tool displays Low Pressure/Normal.
The current state of the input from the A/C low pressure switch. The scan
tool displays Low Pressure when the switch is open and displays Normal when
the switch is closed. The low pressure switch opens when low side pressure
decreases to approximately 151 kPa (22 psi) and closes when the low
side pressure increases to approximately 275 kPa (40 psi).
Recirculate Switch: The scan tool displays On/Off. The
scan tool displays On when the recirculation switch is active. The scan tool
displays Off when the recirculation switch is inactive.
RH AC Duct Actual: The scan tool displays 0-255
counts. The voltage applied to the right upper duct air temperature input
of the HVAC control module is converted to a number between 0 and 255 where
51 Counts is approximately equal to 1 V.
RH AC Duct Desired: The scan tool displays 0-255
counts. The desired value of the right upper duct air temperature input.
The HVAC control module monitors the actual value of the duct air temperature
input and accordingly positions the right air temperature door to achieve
the desired duct air temperature.
RH Heater Duct Actual: The scan tool displays 0-255
counts. The voltage applied to the right lower duct air temperature input
of the HVAC control module is converted to a number between 0 and 255 where
51 Counts is approximately equal to 1 V.
RH Heater Duct Desired: The scan tool displays 0-255
counts. The desired value of the right lower duct air temperature input.
The HVAC control module monitors the actual value of the duct air temperature
input and accordingly positions the right air temperature door to achieve
the desired duct air temperature.
Right Mix Door Actual: The scan tool displays 0-255
counts. The voltage applied to the right air temperature door position input
of the HVAC control module is converted to a number between 0 and 255 where
51 Counts is approximately equal to 1 V.
Right Motor Drive: The scan tool displays Stop, Increase,
or Decrease. The scan tool displays the control decision for the actuator
output as determined by the HVAC control module.
Right Solar Sensor: The scan tool displays 0-255
counts. The voltage applied to the BCM input from the right sunload sensor
is converted to a number between 0 and 255 where 51 Counts is approximately
equal to 1 V.
Right Temp. Setting: The scan tool displays 15 to 32°C
(60 to 90°F). The scan tool displays the selected temperature from the
right air temperature switch.