Step | Action | Yes | No | ||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
1 | Were you sent here from the A/C System Performance Test? | Go to Step 2 | |||||||||
2 | After continued operation of the A/C system, do the low and high side pressures equalize or become static ? | Go to Step 5 | Go to Step 3 | ||||||||
3 | Refer to the pressures recorded during the A/C System Performance Test. Inspect for the following conditions: Caution: Refer to Moving Parts and Hot Surfaces Caution in the Preface section.
Do the listed conditions exist? | Go to Step 5 | Go to Step 4 | ||||||||
4 | Refer to the pressures recorded during the A/C System Performance Test. Inspect for the following conditions: Caution: Refer to Moving Parts and Hot Surfaces Caution in the Preface section.
Do the listed conditions exist ? | Go to Step 5 | |||||||||
5 |
Is the procedure complete? | Go to Step 6 | -- | ||||||||
6 |
Are the readings within the specified ranges? | Go to Step 13 | Go to Step 7 | ||||||||
7 |
Are there metal flakes on the expansion device? | Go to Step 9 | Go to Step 8 | ||||||||
8 | Inspect the expansion device for a brown, powdery residue indicating desiccant in the A/C system. Is there a brown, powdery residue present? | Go to Step 11 | Go to Step 12 | ||||||||
9 |
Is there metal flake contamination present? | Go to Step 12 | Go to Step 12 | ||||||||
10 |
Is the repair complete? | Go to Step 13 | -- | ||||||||
11 |
Is the repair complete? | Go to Step 13 | -- | ||||||||
12 |
Is the repair complete? | Go to Step 13 | -- | ||||||||
13 | Operate the system in order to verify the repair. Did you correct the condition? | System OK |