The internal fault detection is handled inside the control module. No external circuits are involved.
The microprocessor runs the program to detect an internal fault when power up is commanded. The only requirements are voltage and ground. This program runs even if the voltage is out of the valid operating range.
The microprocessor refuses all additional inputs.
• | A current DTC clears when the malfunction is no longer present. |
• | A history DTC clears when the module ignition cycle counter reaches the reset threshold, without a repeat of the malfunction. |
• | This DTC may be stored as a History DTC with out affecting the operation of the module. If stored only as a History DTC and not retrieved as a current DTC, do not replace the module. |
• | If this DTC is retrieved as both a Current and History DTC, replace the module. |
Step | Action | Yes | No |
---|---|---|---|
Important: Refer to Control Module References for schematics, diagnostic system checks, and repair procedures. | |||
1 | Did you perform the Diagnostic System Check for the system exhibiting the symptom? | Go to Step 2 | |
2 |
Is DTC retrieved as a current DTC? | Go to Step 3 | Go to Diagnostic Aids |
3 |
Important: Perform the programming or setup procedure for the module if required. Refer to Control Module References . Did you complete the replacement? | Go to Step 4 | -- |
4 |
Does the DTC reset? | Go to Step 2 | System OK |