The recirculation actuator is an electronic device that incorporates a stepper motor and feedback potentiometer. The HVAC control module controls the recirculation door position by sending a control signal to the actuator. The signal's value is dependent upon the desired mode selected by the vehicle occupants. As the actuator moves, the potentiometer produces the actual door position signal that is sent to the HVAC control module. The HVAC control module continues to command the actuator to move until the desired and actual values are equal. The door directs airflow through the outlets as selected by the vehicles occupants.
• | The ignition is ON. |
• | Ignition voltage is between 9-16 volts. |
• | An mode actuator positional change is attempted. |
The actual mode door position differs from the commanded mode door position by 4 counts or more.
The mode actuator is considered stalled and the HVAC control module will command the mode actuator to stop rotation (2.5 V).
• | If the HVAC control module no longer detects a failure, then the DTC will become history. |
• | The history DTC will clear after 50 ignition cycles without a failure. |
• | The DTC can be cleared with a scan tool. |
• | A dead zone exists in a range 10 counts above or below the mode door max or mode door min positions. When the mode door actual data parameter is within the dead zone, the DTC will not set. If the mode door commanded data parameter differs from the mode door actual data parameter by 4 counts or more outside the dead zone, the DTC will set. |
• | A damaged or broken recirculation door and or actuator can cause this DTC to set. |
Step | Action | Value(s) | Yes | No | ||||||
---|---|---|---|---|---|---|---|---|---|---|
Schematic Reference: HVAC Air Delivery/Temperature Control Schematics | ||||||||||
1 | Did you perform the HVAC Diagnostic System Check? | -- | Go to Step 2 | Go to Diagnostic System Check | ||||||
2 |
Does the scan tool indicate that the recirculation actuator Commanded data parameter is within the specified value of the recirculation actuator Actual data parameter? | 0-3 counts | Go to Testing for Intermittent Conditions and Poor Connections | Go to Step 3 | ||||||
3 |
Does the scan tool indicate that the recirculation actuator actual parameter changes within the specified range when it is commanded from REC to OSA? | 5-250 counts | Go to diagnostic aids | Go to Step 4 | ||||||
4 | Test the recirculation actuator ignition 3 circuit for an open. Refer to Circuit Testing and Wiring Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 13 | Go to Step 5 | ||||||
5 | Test the 5 volt reference circuit of the recirculation actuator for an open. Refer to Circuit Testing and Wiring Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 13 | Go to Step 6 | ||||||
6 | Test the recirculation door motor control circuit for an open, short to ground or short to voltage. Refer to Circuit Testing and Wiring Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 13 | Go to Step 7 | ||||||
7 |
Important: The air temperature actuator connector and the HVAC control module connector must be connected to correctly perform test.
Does the recirculation actuator drive shaft rotate and do the counts change? | -- | Go to Step 10 | Go to Step 8 | ||||||
8 | Inspect the recirculation actuator and the recirculation actuator for the following:
Did you find and correct the condition? | -- | Go to Step 13 | Go to Step 9 | ||||||
9 | Inspect for poor connections at the harness connector of the recirculation actuator. Refer to Testing for Intermittent Conditions and Poor Connections and Connector Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 13 | Go to Step 11 | ||||||
10 | Inspect for poor connections at the harness connector of the HVAC control module. Refer to Testing for Intermittent Conditions and Poor Connections and Connector Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 13 | Go to Step 12 | ||||||
11 | Replace the recirculation actuator. Did you complete the replacement? | -- | Go to Step 13 | -- | ||||||
12 |
Important: Perform the recalibration procedure for the HVAC control module. Replace the HVAC control module. Refer to Control Assembly Replacement . Did you complete the replacement? | -- | Go to Step 13 | -- | ||||||
13 |
Does the DTC reset? | -- | Go to Step 2 | System OK |