• | The condition may be intermittent. Refer to Testing for Intermittent Conditions and Poor Connections in Wiring Systems. |
• | Inspect the air delivery system for the following conditions: |
• | An obstruction to the airflow |
• | Air leaks |
• | Misaligned air ducts |
• | Broken or binding linkages or doors |
Step | Action | Yes | No |
---|---|---|---|
Schematic Reference: HVAC Schematics Connector End View Reference: HVAC Connector End Views | |||
1 | Did you perform the HVAC Diagnostic System Check? | Go to Step 2 | |
2 |
Is the blower motor OFF? | Go to Step 3 | Go to Blower Motor Always On |
3 | Place the blower motor switch in each speed position. Does the blower motor operate in any of the speed positions? | Go to Step 4 | Go to Blower Motor Inoperative |
4 | Does the blower motor operate in each speed position? | Go to Step 5 | Go to Blower Motor Malfunction |
5 |
Does the scan tool indicate that the Mode Switch parameter changes state? | Go to Step 6 | Go to Step 7 |
6 |
Does the recirculation door move from the recirculation position to the outside air position? | Go to Diagnostic Aids | |
7 | Inspect for poor connections at the harness connector of the HVAC control module. Refer to Testing for Intermittent Conditions and Poor Connections and Connector Repairs in Wiring Systems. Did you find and correct the condition? | Go to Step 9 | Go to Step 8 |
8 | Replace the HVAC control module. Refer to HVAC Control Module Replacement . Did you complete the replacement? | Go to Step 9 | -- |
9 | Operate the system in order to verify the repair. Did you correct the condition? | System OK | Go to Step 2 |