A/C Compressor Feedback: The scan tool displays On/Off. The
state of the HVAC control module input for the A/C compressor status. When supply
voltage is applied to the A/C compressor clutch coil, the voltage is also applied
to the input terminal of the HVAC control module and the scan tool displays On. The
scan tool displays Off when supply voltage is not applied to the A/C compressor clutch
coil.
A/C Head Pressure: The scan tool displays Yes/No. The scan tool
displays Yes when the HVAC control module receives a class 2 message from the
PCM that the A/C high side pressure is at or above 2413 kPa (350 psi).
This action disables an A/C request. The scan tool displays No when the HVAC control
module receives a class 2 message from the PCM that the A/C high side pressure
is below 2413 kPa (350 psi).
A/C High Side Pressure Sensor: The scan tool displays 0-3450 kPa
(0-500 psi). The voltage applied to the PCM input from the A/C refrigerant
pressure sensor is converted to a pressure value.
A/C High Side Pressure Sensor: The scan tool displays 0-5 volts.
The voltage applied to the PCM input for the A/C refrigerant pressure sensor.
A/C Switch: The scan tool displays On/Off. The scan tool displays
On when the A/C request switch is active. The scan tool displays Off when the A/C
request switch is inactive.
A/C Permission: The scan tool displays Withheld/Granted. The
scan tool displays Granted when the HVAC control module determines that conditions
for compressor clutch engagement are present. The scan tool displays Withheld when
the HVAC control module determines that conditions for compressor clutch engagement
are not present.
A/C Heater Door Actual: The scan tool displays 0-255 Counts.
The voltage applied to the HVAC control module input for the mode door position is
converted to a number between 0 and 255 where 51 Counts is approximately
equal to 1 V.
A/C Heater Door Commanded: The scan tool displays 0-255 counts.
The scan tool displays the desired mode door position as determined by the HVAC control
module.
A/C Heater Motor Drive: The scan tool displays Stop, Increase,
or Decrease. The scan tool displays the control decision for the actuator output
as determined by the HVAC control module.
A/C Relay Command: The scan tool displays On/Off. The scan tool
displays the control decision for the compressor clutch relay output as determined
by the PCM.
A/C Request Signal: The scan tool displays Yes/No. The scan
tool displays Yes when the PCM receives a class 2 message from the HVAC control
module to engage the A/C compressor clutch. The scan tool displays No when the PCM
receives a class 2 message from the HVAC control module to disengage the
A/C compressor clutch.
Air Inlet Commanded: The scan tool displays 0-255 counts.
The scan tool displays the desired recirculation door position as determined by the
HVAC control module.
Air Inlet Door Actual: The scan tool displays 0-255 counts.
The voltage applied to the recirculation door position input of the HVAC control
module is converted to a number between 0 and 255 where 51 Counts is approximately
equal to 1 V.
Air Inlet Drive Motor: The scan tool displays Stop, Increase,
or Decrease. The scan tool displays the control decision for the actuator output
as determined by the HVAC control module.
Air Mix Door Actual: The scan tool displays 0-255 counts.
The voltage applied to the auxiliary air temperature door position input of the auxiliary
HVAC control module is converted to a number between 0 and 255 where 51 Counts
is approximately equal to 1 V.
Air Mix Door Commanded: The scan tool displays 0-255 counts.
The scan tool displays the desired auxiliary air temperature door position as determined
by the auxiliary HVAC control module.
Air Mix Door Left Commanded: The scan tool displays 0-255 counts.
The scan tool displays the desired left air temperature door position as determined
by the HVAC control module.
Air Mix Door Right Commanded: The scan tool displays 0-255 counts.
The scan tool displays the desired right air temperature door position as determined
by the HVAC control module.
Auto Switch: The scan tool displays On/Off. The scan tool displays
On when the automatic switch is active. The scan tool displays Off when the automatic
switch is inactive.
Battery Voltage: The scan tool displays 0-25 volts.
The voltage measured from the battery positive voltage circuit and the ground circuit
of the HVAC control module.
Battery Voltage: The scan tool displays 0-25 volts.
The voltage measured from the battery positive voltage circuit and the ground circuit
of the auxiliary HVAC control module.
Blower Motor PWM: The scan tool displays 0-89%. The scan
tool displays the control decision for the blower motor speed as determined by the
HVAC control module. The scan tool displays 89% when the blower motor
is commanded to maximum speed. The scan tool displays 0% when the blower motor is
commanded OFF.
Blower Speed: The scan tool displays Yes/No. The scan tool displays
Yes when the ignition switch is placed from the Run position to the Crank position.
The scan tool displays No during all other ignition switch positions.
Console Mode Door Actual: The scan tool displays 0-255 counts.
The scan tool displays the desired console mode door position as determined by the
auxiliary HVAC control module.
Console Mode Door Commanded: The scan tool displays 0-255 counts.
The scan tool displays the desired console mode door position as determined by the
auxiliary HVAC control module.
Defrost Door Actual: The scan tool displays 0-255 counts.
The voltage applied to the defrost door position input of the HVAC control module
is converted to a number between 0 and 255 where 51 Counts is approximately
equal to 1 V.
Defrost Door Commanded: The scan tool displays 0-255 counts.
The scan tool displays the desired defrost door position as determined by the HVAC
control module.
Defrost Motor Drive: The scan tool displays Stop, Increase,
or Decrease. The scan tool displays the control decision for the actuator output
as determined by the HVAC control module.
Driver Override Switch: The scan tool displays Rear, Off, Low,
Med, or High. The scan tool displays the position of the front auxiliary blower motor
switch as determined by the auxiliary HVAC control module.
ECT Sensor: The scan tool displays -39 to 140°C (-38 to
284°F) . The voltage applied to the PCM input from the engine coolant temperature
sensor is converted to a temperature value.
Engine Coolant Temp: The scan tool displays Yes/No. The scan
tool displays Yes when the HVAC control module receives a class 2 message from
the PCM that the engine coolant temperature is at or above 123°C (253°F).
This action disables an A/C request. The scan tool displays No when the engine coolant
temperature is below 123°C (253°F).
Engine Running: The scan tool displays Yes/No. The scan tool
displays Yes when the HVAC control module receives a class 2 message from the
PCM that the engine is not running. This action disables an A/C request. The scan
tool displays No when the HVAC control module receives a class 2 message from
the PCM that the engine is running.
Fan Down Button: The scan tool displays On/Off. The scan tool
displays On when the fan down switch is active. The scan tool displays Off when the
fan down switch is inactive.
Fan Up Button: The scan tool displays On/Off. The scan tool
displays On when the fan up switch is active. The scan tool displays Off when the
fan up switch is inactive.
Front Defrost Switch: The scan tool displays On/Off. The scan
tool displays On when the defrost switch is active. The scan tool displays Off when
the defrost switch is inactive.
Heater Water Valve: The scan tool displays Open or Closed. The
scan tool displays the commanded state of the coolant bypass valve.
Ign. Since Current DTC: The scan tool displays 0-100.
The number of the ignition cycles since the setting of the most recent current diagnostic
trouble code (DTC).
Inside Air Temp Fan: The scan tool displays On/Off. The scan
tool displays the control decision for the fan motor output as determined by the
HVAC control module. The fan motor is internal to the inside air temperature sensor
assembly.
Inside Air Temp: The scan tool displays -40 to 215°C
(-40 to 419°F). The voltage applied to the HVAC control module input for the
inside air temperature sensor is converted to a temperature value.
Left Mix Door Actual: The scan tool displays 0-255 counts.
The voltage applied to the left air temperature door position input of the HVAC control
module is converted to a number between 0 and 255 where 51 Counts is approximately
equal to 1 V.
Left Mix Motor Drive: The scan tool displays Stop, Increase,
or Decrease. The scan tool displays the control decision for the actuator output
as determined by the HVAC control module.
Left Solar Sensor: The scan tool displays 0-255 counts.
The voltage applied to the left sunload input of the BCM is converted to a number
between 0 and 255 where 51 Counts is approximately equal to 1 V.
Left Temp. Setting: The scan tool displays 15 to 32°C (60
to 90°F). The scan tool displays the selected temperature from the left air temperature
switch.
LH AC Duct Actual: The scan tool displays 0-255 counts.
The voltage applied to the left upper duct air temperature input of the HVAC control
module is converted to a number between 0 and 255 where 51 Counts is approximately
equal to 1 V.
LH AC Duct Desired: The scan tool displays 0-255 counts.
The desired value of the left upper duct air temperature input. The HVAC control
module monitors the actual value of the duct air temperature input and accordingly
positions the left air temperature door to achieve the desired duct air temperature.
LH Heater Duct Actual: The scan tool displays 0-255 counts.
The voltage applied to the left lower duct air temperature input of the HVAC control
module is converted to a number between 0 and 255 where 51 Counts is approximately
equal to 1 V.
LH Heater Duct Desired: The scan tool displays 0-255 counts.
The desired value of the left lower duct air temperature input. The HVAC control
module monitors the actual value of the duct air temperature input and accordingly
positions the left air temperature door to achieve the desired duct air temperature.
Mode Door Actual: The scan tool displays 0-255 counts.
The voltage applied to the auxiliary mode door position input of the auxiliary HVAC
control module is converted to a number between 0 and 255 where 51 Counts
is approximately equal to 1 V.
Mode Door Commanded: The scan tool displays 0-255 counts.
The scan tool displays the desired auxiliary mode door position as determined by
the auxiliary HVAC control module.
Mode Select Position: The scan tool displays Off, Auto, Defrost,
Heater, Htr/Def, Bi-Level, Panel. The scan tool displays the state of mode operation.
Mode Switch: The scan tool displays On/Off. The scan tool displays
On when the mode switch is active. The scan tool displays Off when the mode switch
is inactive.
Off Switch: The scan tool displays On/Off. The scan tool displays
On when the Off switch is active. The scan tool displays Off when the Off switch
is inactive.
Outside Air Temp: The scan tool displays Yes/No. The scan tool
displays Yes when the HVAC control module interprets the input of the ambient air
temperature sensor is at or below 1°C (35°F). This action disables an A/C
request. The scan tool displays No when the HVAC control module interprets the input
of the ambient air temperature sensor is above 1°C (35°F).
Outside Air Temp. Filtered: The scan tool displays -40
to 215°C (-40 to 419°F). The current value of the ambient air temperature
display on the HVAC control module.
Outside Air Temp. Raw: The scan tool displays -40 to
215°C (-40 to 419°F). The voltage applied to the HVAC control module input
from the ambient air temperature sensor is converted to an unfiltered temperature
value.
Pressure Cycle Switch: The scan tool displays Yes/No. The scan
tool displays Yes when the HVAC control module interprets the input of the A/C low
pressure switch is not grounded. This action disables an A/C request. The scan tool
displays No when the HVAC control module interprets the input of the A/C low pressure
switch is grounded.
Pressure Cycle Switch: The scan tool displays Low Pressure/Normal.
The current state of the input from the A/C low pressure switch. The scan tool displays
Low Pressure when the switch is open and displays Normal when the switch is closed.
The low pressure switch opens when low side pressure decreases to approximately
151 kPa (22 psi) and closes when the low side pressure increases to approximately
275 kPa (40 psi).
Rear Blower Speed: The scan tool displays %. The commanded state
of the auxiliary blower motor as determined by the auxiliary HVAC control module.
Rear HVAC Fan Down Switch: The scan tool displays Active or
Inactive. The scan tool displays Active when the fan down switch is pressed. The
scan tool displays Inactive when the fan down switch is not used.
Rear HVAC Fan Speed (VIN 3): The scan tool displays Off, Med,
or High. The commanded state of the auxiliary blower motor as determined by the auxiliary
HVAC control module.
Rear HVAC Fan Speed (VIN 6): The scan tool displays Off, Low,
Med or High. The commanded state of the auxiliary blower motor as determined by the
auxiliary HVAC control module.
Rear HVAC Fan Up Switch: The scan tool displays Active or Inactive.
The scan tool displays Active when the fan down switch is pressed. The scan tool
displays Inactive when the fan down switch is not used.
Rear HVAC Mode Switch: The scan tool displays Active or Inactive.
The scan tool displays Active when the auxiliary mode switch is pressed. The scan
tool displays Inactive when the auxiliary mode switch is not used.
Rear HVAC Motor Pos.: The scan tool displays Lower, Bi-level
or Upper. The actual auxiliary mode door position as determined auxiliary HVAC control
module.
Recirculate Switch: The scan tool displays On/Off. The scan
tool displays On when the recirculation switch is active. The scan tool displays
Off when the recirculation switch is inactive.
Rec. Mode from Front Control: The scan tool displays Heater,
Panel, Defrost, Bi-level or Htr./Def. The state of the primary HVAC system, received
by class 2 message, as determined by the auxiliary HVAC control module.
RH AC Duct Actual: The scan tool displays 0-255 counts.
The voltage applied to the right upper duct air temperature input of the HVAC control
module is converted to a number between 0 and 255 where 51 Counts is approximately
equal to 1 V.
RH AC Duct Desired: The scan tool displays 0-255 counts.
The desired value of the right upper duct air temperature input. The HVAC control
module monitors the actual value of the duct air temperature input and accordingly
positions the right air temperature door to achieve the desired duct air temperature.
RH Heater Duct Actual: The scan tool displays 0-255 counts.
The voltage applied to the right lower duct air temperature input of the HVAC control
module is converted to a number between 0 and 255 where 51 Counts is approximately
equal to 1 V.
RH Heater Duct Desired: The scan tool displays 0-255 counts.
The desired value of the right lower duct air temperature input. The HVAC control
module monitors the actual value of the duct air temperature input and accordingly
positions the right air temperature door to achieve the desired duct air temperature.
Right Mix Door Actual: The scan tool displays 0-255 counts.
The voltage applied to the right air temperature door position input of the HVAC
control module is converted to a number between 0 and 255 where 51 Counts
is approximately equal to 1 V.
Right Mix Motor Drive: The scan tool displays Stop, Increase,
or Decrease. The scan tool displays the control decision for the actuator output as
determined by the HVAC control module.
Right Solar Sensor: The scan tool displays 0-255 counts.
The voltage applied to the BCM input from the right sunload sensor is converted to
a number between 0 and 255 where 51 Counts is approximately equal to 1 V.
Right Temp. Setting: The scan tool displays 15 to 32°C (60
to 90°F). The scan tool displays the selected temperature from the right air
temperature switch.
SWC Switch Power: The scan tool displays On/Off. The scan tool
displays the control decision for the supply voltage output to the steering wheel
controls as determined by the BCM.
SWC Switch Voltage: The scan tool display 0-5 volts. The
scan tool displays the voltage applied to the BCM input from the steering wheel controls.