AC Compressor Feedback: The scan tool displays On/Off. The state
of the HVAC control module input for the A/C compressor status. When supply voltage
is applied to the A/C compressor clutch coil, the voltage is also applied to the
input terminal of the HVAC control module and the scan tool displays On. The scan
tool displays Off when supply voltage is not applied to the A/C compressor clutch
coil.
A/C Head Pressure: The scan tool displays Yes/No. The scan tool
displays Yes when the HVAC control module receives a class 2 message from the
PCM that the A/C high side pressure is at or above 2413 kPa (350 psi).
This action disables an A/C request. The scan tool displays No when the HVAC control
module receives a class 2 message from the PCM that the A/C high side pressure
is below 2413 kPa (350 psi).
A/C High Side Pressure : The scan tool displays 0-3450
kPa (0-500 psi). The voltage applied to the PCM input from the A/C refrigerant
pressure sensor is converted to a pressure value.
A/C High Side Pressure : The scan tool displays 0-5 volts.
The voltage applied to the PCM input for the A/C refrigerant pressure sensor.
A/C Switch: The scan tool displays On/Off. The scan tool displays
On when the A/C request switch is active. The scan tool displays Off when the A/C
request switch is inactive.
AC Permission: The scan tool displays Withheld/Granted. The
scan tool displays Granted when the HVAC control module determines that conditions
for compressor clutch engagement are present. The scan tool displays Withheld when
the HVAC control module determines that conditions for compressor clutch engagement
are not present.
AC/Heater Door Actual: The scan tool displays 0-255 Counts.
The voltage applied to the HVAC control module input for the mode door position
is converted to a number between 0 and 255 where 51 Counts is approximately
equal to 1 V.
AC/Heater Door Commanded: The scan tool displays 0-255
counts. The scan tool displays the desired mode door position as determined by the
HVAC control module.
AC/Heater Motor Drive: The scan tool displays Stop, Increase,
or Decrease. The scan tool displays the control decision for the actuator output
as determined by the HVAC control module.
A/C Relay Command: The scan tool displays On/Off. The scan tool
displays the control decision for the compressor clutch relay output as determined
by the PCM.
A/C Request Signal: The scan tool displays Yes/No. The scan
tool displays Yes when the PCM receives a class 2 message from the HVAC control
module to engage the A/C compressor clutch. The scan tool displays No when the
PCM receives a class 2 message from the HVAC control module to disengage
the A/C compressor clutch.
Air Mix Door Actual: The scan tool displays 0-255 counts.
The voltage applied to the auxiliary air temperature door position input of the
auxiliary HVAC control module is converted to a number between 0 and 255 where 51 Counts
is approximately equal to 1 V.
Air Mix Door Commanded: The scan tool displays 0-255 counts.
The scan tool displays the desired auxiliary air temperature door position as determined
by the auxiliary HVAC control module.
Air Mix Door Left Commanded: The scan tool displays 0-255
counts. The scan tool displays the desired left air temperature door position as
determined by the HVAC control module.
Air Mix Door Right Commanded: The scan tool displays 0-255
counts. The scan tool displays the desired right air temperature door position as
determined by the HVAC control module.
Battery Voltage: The scan tool displays 0-25 volts. The
voltage measured from the battery positive voltage circuit and the ground circuit
of the HVAC control module.
Battery Voltage: The scan tool displays 0-25 volts. The
voltage measured from the battery positive voltage circuit and the ground circuit
of the auxiliary HVAC control module.
Blower Speed: The scan tool displays Yes/No. The
scan tool displays Yes when the HVAC control module interprets the input of the Off
blower motor control circuit has battery positive voltage. This action disables an
A/C request. The scan tool displays No when the HVAC control module interprets the
input of the Off blower motor control circuit has no voltage.
Console Mode Door Actual: The scan tool displays 0-255
counts. The scan tool displays the desired console mode door position as determined
by the auxiliary HVAC control module.
Console Mode Door Commanded: The scan tool displays 0-255
counts. The scan tool displays the desired console mode door position as determined
by the auxiliary HVAC control module.
Defrost Door Actual: The scan tool displays 0-255 counts.
The voltage applied to the defrost door position input of the HVAC control module
is converted to a number between 0 and 255 where 51 Counts is approximately
equal to 1 V.
Defrost Door Commanded: The scan tool displays 0-255 counts.
The scan tool displays the desired defrost door position as determined by the HVAC
control module.
Defrost Motor Drive: The scan tool displays Stop, Increase,
or Decrease. The scan tool displays the control decision for the actuator output
as determined by the HVAC control module.
Driver Override Switch: The scan tool displays Rear, Off, Low,
Med, or High. The scan tool displays the position of the front auxiliary blower
motor switch as determined by the auxiliary HVAC control module.
ECT Sensor: The scan tool displays -39 to 140°C (-38 to
284°F) . The voltage applied to the PCM input from the engine coolant temperature
sensor is converted to a temperature value.
Engine Coolant Temp: The scan tool displays Yes/No. The scan
tool displays Yes when the HVAC control module receives a class 2 message from
the PCM that the engine coolant temperature is at or above 123°C (253°F).
This action disables an A/C request. The scan tool displays No when the engine coolant
temperature is below 123°C (253°F).
Engine Running: The scan tool displays Yes/No. The scan tool
displays Yes when the HVAC control module receives a class 2 message from the
PCM that the engine is not running. This action disables an A/C request. The scan
tool displays No when the HVAC control module receives a class 2 message from
the PCM that the engine is running.
Heater Water Valve: The scan tool displays Open or Closed.
The scan tool displays the commanded state of the coolant bypass valve.
Ign. Since Current DTC: The scan tool displays 0-100.
The number of the ignition cycles since the setting of the most recent current diagnostic
trouble code (DTC).
Left Mix Door Actual: The scan tool displays 0-255 counts.
The voltage applied to the left air temperature door position input of the HVAC
control module is converted to a number between 0 and 255 where 51 Counts
is approximately equal to 1 V.
Left Motor Drive: The scan tool displays Stop, Increase, or
Decrease. The scan tool displays the control decision for the actuator output as
determined by the HVAC control module.
Left Solar Sensor: The scan tool displays 0-255 counts.
The voltage applied to the left sunload input of the BCM is converted to a number
between 0 and 255 where 51 Counts is approximately equal to 1 V.
Left Temp. Detent Pos.: The scan tool displays a value from
0 to 18. The scan tool displays the position of the left air temperature switch.
0 is displayed for a full cold position. 18 is displayed for a full hot position.
Mode Door Actual: The scan tool displays 0-255 counts.
The voltage applied to the auxiliary mode door position input of the auxiliary HVAC
control module is converted to a number between 0 and 255 where 51 Counts
is approximately equal to 1 V.
Mode Door Commanded: The scan tool displays 0-255 counts.
The scan tool displays the desired auxiliary mode door position as determined by
the auxiliary HVAC control module.
Mode Select Position: The scan tool displays Off, Auto, Defrost,
Heater, Htr/Def, Bi-Level, Panel. The scan tool displays the state of mode operation.
Outside Air Temp: The scan tool displays Yes/No. The scan tool
displays Yes when the HVAC control module interprets the input of the ambient air
temperature sensor is at or below 1°C (35°F). This action disables an A/C
request. The scan tool displays No when the HVAC control module interprets the input
of the ambient air temperature sensor is above 1°C (35°F).
Pressure Cycle Switch: The scan tool displays Yes/No. The scan
tool displays Yes when the HVAC control module interprets the input of the A/C low
pressure switch is not grounded. This action disables an A/C request. The scan tool
displays No when the HVAC control module interprets the input of the A/C low pressure
switch is grounded.
Pressure Cycle Switch: The scan tool displays Low Pressure/Normal.
The current state of the input from the A/C low pressure switch. The scan tool displays
Low Pressure when the switch is open and displays Normal when the switch is closed.
The low pressure switch opens when low side pressure decreases to approximately
151 kPa (22 psi) and closes when the low side pressure increases to approximately
275 kPa (40 psi).
Rear Blower Speed: The scan tool displays Off, Low, Med or High.
The commanded state of the auxiliary blower motor as determined by the auxiliary
HVAC control module.
Rear HVAC Fan Speed: The scan tool displays Off, Low, Med or
High. The commanded state of the auxiliary blower motor as determined by the auxiliary
HVAC control module.
Rear HVAC Motor Pos.: The scan tool displays Lower, Bi-level
or Upper. The actual auxiliary mode door position as determined auxiliary HVAC control
module.
Rear Temp. Select Sw.: The scan tool displays a value from 1
to 13 Counts. The scan tool displays the position of the auxiliary air temperature
switch. 1 Counts is displayed for a full cold position. 13 Counts is displayed for
a full hot position.
Recirculate Switch: The scan tool displays On/Off. The scan
tool displays On when the recirculation switch is active. The scan tool displays
Off when the recirculation switch is inactive.
Rec. Mode from Front Control: The scan tool displays Heater,
Panel, Defrost, Bi-level or Htr./Def. The state of the primary HVAC system, received
by class 2 message, as determined by the auxiliary HVAC control module.
Right Mix Door Actual: The scan tool displays 0-255 counts.
The voltage applied to the right air temperature door position input of the HVAC
control module is converted to a number between 0 and 255 where 51 Counts
is approximately equal to 1 V.
Right Motor Drive: The scan tool displays Stop, Increase, or
Decrease. The scan tool displays the control decision for the actuator output as
determined by the HVAC control module.
Right Temp. Detent Pos.: The scan tool displays a value from
0 to 18. The scan tool displays the position of the right air temperature switch.
0 is displayed for a full cold position. 18 is displayed for a full hot position.
SWC Power: The scan tool displays On/Off. The scan tool displays
the control decision for the supply voltage output to the steering wheel controls
as determined by the BCM.
SWC Switch Voltage: The scan tool display 0-5 volts. The
scan tool displays the voltage applied to the BCM input from the steering wheel
controls.