Delphi CS-144 (KG9) and Valeo A13VI+ (K68)
When the charging system is operating normally, the charge indicator
lamp will come on when the ignition switch is turned ON and will go out when
the engine starts. If the lamp operates abnormally, refer to
Charge Indicator Always On
or
Charge Indicator Inoperative
. If an undercharged or
overcharged battery condition occurs, refer to
Battery Is Undercharged or Overcharged
. Automotive generators produce
a certain amount of low level sound during normal operation. This sound is
caused by a combination of mechanical and electrical/magnetic conditions in
the generator. Typically, the sound level will be higher during periods of
high output demand on the generator. Objectionable noise from a generator
may be caused by conditions causing normal sound to be transmitted directly
to the passenger compartment, by mounting problems, or by internal generator
conditions. The following can cause objectionable noise:
• | Improper routing of hoses, wiring, shielding, etc., against the
generator housing. |
• | Mounting the generator in a bind. |
• | A faulty or damaged diode, stator, or rotor |
Delphi CS-144 (KG9)
Tools Required
J 41450-B J 41450-B
To diagnose a CS generator use the following procedure:
- Turn the ignition switch OFF. Turn all electrical accessory loads
OFF.
- Turn the load in the carbon pile load tester all the way OFF.
Connect load test across the battery terminals. Refer to
Starting and Charging Schematics
to be sure the
ammeter clip is placed for the entire generator output to pass through the
clip. If circuits are split so that any of the current can pass through parallel
circuits, all such circuits must pass through the clip or the generator output
reading on the inductive ammeter will not be accurate.
- Install the inductive ammeter around the output wire(s) of the
generator.
- Perform the universal tester self-test procedure per the manufacturer's
instructions to verify proper operation of the tester.
- Connect the red alligator clip of the tester to the generator
output terminal. Connect the black clip to the metal generator housing. The
green POWER lamp on the tester should light. If the green POWER lamp does
light, go to step 8. If the green POWER lamp does not light, go to step 6.
- Use a digital multimeter to check the voltage between the generator
output terminal and the battery negative terminal. If the reading is B+ voltage,
go to step 7. If not, check for an open condition in the generator output
wiring and repair as necessary. If the tester's green POWER lamp now lights
when connected per step 5, go to step 8. If no open condition was found or
the green POWER lamp still does not light, go to step 7.
- With the tester still connected as described in step 5, connect
a jumper wire between the generator metal housing and the battery negative
terminal. The green POWER lamp on the tester should light. If the green POWER
lamp does light, check the ground path from the generator housing to the battery
negative terminal for open conditions and repair as necessary. If the tester's
green POWER lamp now lights, go to step 8. If not, return to step 1 and repeat
the procedure, including the tester self-test.
- With the tester still connected as described in step 5, disconnect
the 4-way generator connector from the generator and connect the matching
connector on the tester to the generator. The red DIAGNOSTIC lamp on the tester
should light. If the red DIAGNOSTIC lamp lights, go to step 10. If the red
DIAGNOSTIC lamp does not light, go to step 9.
- Disconnect the 4-way tester connector from the generator. With
the ignition key in RUN (engine stopped), use a fused jumper lead (with a
5 A fuse) and Metri-Pack 150 terminal probe adapter to ground the L
terminal (cavity B) in the vehicle harness 4-way connector. If the fuse does
not blow, replace the generator. If the fuse blows, refer to
Starting and Charging Schematics
to diagnose
and repair the L terminal circuit (225) for direct short to B+ or mis-wired/no
resistance condition, then replace the generator. Fix the wiring before replacing
the generator.
- Turn OFF all the electrical accessories and close the doors to
be sure all the loads are off. With the tester connected as described in step
8, start the engine and let the engine idle briefly. (Note that the vehicle's
generator control circuits are bypassed during this test, and the charge indicator
in the instrument cluster will not operate normally.) After the engine starts,
the red DIAGNOSTIC lamp on the tester should not be lit. If the red DIAGNOSTIC
lamp is still lit, replace the generator. If the red DIAGNOSTIC lamp is not
lit, go to step 11.
- Increase the engine speed to 2500 RPM. The red DIAGNOSTIC lamp
on the tester should not light. If the red DIAGNOSTIC lamp lights, replace
the generator. If the red DIAGNOSTIC lamp is not lit, go to step 12.
- With the engine speed still at 2500 RPM, turn the load on the
carbon pile load tester to ON and adjust until the generator output is at
the load test value. Refer to
Generator Usage
. If the red DIAGNOSTIC lamp on the tester lights with the generator
operating at or below the load test output value, replace the generator. If
the red light does not light and the load test value is attained, the generator
is good. DO NOT replace the generator. Go to step 13.
- Turn the carbon pile load tester load to OFF and stop the engine.
Remove the generator tester, ammeter, and load tester from the vehicle. Reconnect
the 4-way harness connector to the generator. Be sure the connector is fully
seated and latched.
• | If the customer has commented about erratic or high voltage from
a generator that uses an S terminal connection, be sure to check the S terminal
circuit (cavity D in the harness connector) for intermittent or high resistance
connections. |
Valeo A13VI+ (K68)
Tools Required
J 39200 Digital Multimeter
or equivalent
To diagnose the Valeo A13VI+ (K68) generator, use the following procedure:
- Turn the ignition switch ON without starting the engine.
- Using a DMM, measure and record the battery voltage. The charge
indicator should be on. If the indicator is not lit, disconnect the generator
electrical connector and ground the L terminal in the electrical connector.
• | If the indicator lights, repair or replace the generator. |
• | If the indicator does not light, locate and repair open circuit
between grounding lead and ignition switch. The charge indicator bulb may
be burned out. |
- With ignition switch ON and the engine running, the charge indicator
lamp should not be lit. If the lamp is lit, turn the engine OFF and disconnect
the 4-way harness connector from the generator. Turn the ignition ON and start
the engine.
• | If the charge indicator lamp does not light, repair or replace
the generator. |
• | If the charge indicator lamp is still lit, check for a grounded
L terminal wire in the harness. |
- With the ignition switch ON and the engine not running, connect
the DMM from the ground to the generator connector L terminal. This terminal
should have battery voltage. If low or zero volts is indicated, high
resistance or an open exists in the circuit. Refer to
Starting and Charging Schematics
.
- Connect the DMM from the battery negative terminal to the generator
output BAT terminal. This reading should also be battery voltage. If low or
zero volts is indicated, high resistance or an open exists in the circuit.
Refer to
Starting and Charging Schematics
.
- Reconnect the wiring harness connector to the generator. Start
and run the engine at a moderate speed (above 1000 RPM), with the electrical
loads and accessories OFF.
- Use the DMM to measure the voltage across the battery.
• | If the voltage is above 16 volts, replace the generator. |
• | If the voltage is below the battery voltage measured in step 2,
inspect the circuit between the generator output terminal and the battery
for chafing, corrosion, or breaks. If no problems are found, replace the generator. |
- Disconnect the battery negative cable. Refer to
Battery Negative Cable Disconnection and Connection
.
- Disconnect the wiring harness from the generator output BAT terminal.
Important: Insulate the ammeter to generator and wiring harness connections to
make sure that there is no contact to any exposed metal surfaces that could
potentially cause a short.
- Install an ammeter between the generator output BAT terminal and the
engine wiring harness.
- Reconnect the battery negative cable. Refer to
Battery Negative Cable Disconnection and Connection
.
- With the load test OFF, connect a carbon pile load tester across
the battery terminals.
- Start the engine. Run the engine at a moderate speed (2500 RPM).
- Turn the carbon pile load ON and adjust to the proper load test
value. Refer to
Generator Usage
.
Use the DMM to check the voltage across the battery terminals:
• | If the voltage is above 13 volts, the generator is GOOD. |
• | If the voltage falls below 13 volts, repair or replace the generator. |
• | If the load test value cannot be attained and the voltage falls
below 13 volts, repair or replace the generator. (If load test value can not
be attained but voltage does not fall below 13 volts, a carbon pile tester
problem is indicated. Check for low ampere capacity of test load.) |