GM Service Manual Online
For 1990-2009 cars only

Diagnostic Instructions

    • Perform the Diagnostic System Check - Vehicle prior to using this diagnostic procedure.
    • Review Strategy Based Diagnosis for an overview of the diagnostic approach.
    •  Diagnostic Procedure Instructions provides an overview of each diagnostic category.

Diagnostic Fault Information

Circuit

Short to Ground

Open/High Resistance

Short to Voltage

Signal Performance

Stepper Motors 12 V Reference

B023A 02,

B0223 06,

B022A 06,

B0233 06,

B0408 06,

B0418 06

B0223 06,

B022A 06,

B0233 06,

B0408 06,

B0418 06

--

--

Air Temperature Actuator - Left Control 1

B0408 06

B0408 06

B0408 01

1

Air Temperature Actuator - Left Control 2

B0408 06

B0408 06

B0408 01

1

Air Temperature Actuator - Left Control 3

B0408 06

B0408 06

B0408 01

1

Air Temperature Actuator - Left Control 4

B0408 06

B0408 06

B0408 01

1

Air Temperature Actuator - Right Control 1

B0418 06

B0428 06

B0418 01

1

Air Temperature Actuator - Right Control 2

B0418 06

B0418 06

B0418 01

1

Air Temperature Actuator - Right Control 3

B0418 06

B0418 06

B0418 01

1

Air Temperature Actuator - Right Control 4

B0418 06

B0418 06

B0418 01

1

1. Air Temperature Malfunction

Circuit/System Description

Only C68

With the temperature switch at the HVAC control, the desired air temperature flap position can be put in. The selected value is sent to the HVAC control module via the LIN-Bus. The HVAC control module supplies a 12 V reference voltage to the stepper motor and energizes the 4 stepper motor coils with a pulsed ground signal. The stepper motor puts the mixed air flap into the calculated position, in order to reach the selected temperature.

Only CJ2

With the temperature switches at the HVAC control, the wished air temperature flap position can be put in. The selected values are sent to the HVAC control module via LIN-Bus. The HVAC control module supplies a 12 V reference voltage to the stepper motors and energizes the 4 stepper motor coils with a pulsed ground signal. The stepper motors put the mixed air flaps into the calculated position, in order to reach the put in temperature.

Diagnostic Aids

Check the following mechanical fault sources:

    • Air distribution box
    • Air distribution hoses/air distribution ducts

Reference Information

Schematic Reference

HVAC Schematics

Connector End View Reference

Component Connector End Views

Description and Operation

Automatic HVAC Description and Operation

Electrical Information Reference

    •  Circuit Testing
    •  Connector Repairs
    •  Testing for Intermittent Conditions and Poor Connections
    •  Wiring Repairs

Scan Tool Reference

Control Module References

Circuit/System Verification

  1. Ignition ON, Measure actual inside air temperature using a thermometer. Compare this value to the scan tool Passenger Compartment Air Temperature parameter. The measured temperature should be within 5°C (9°F) difference of parameter value.
  2. If not within the specified range, refer to DTC B0163, B0183, or B1405
  3. Measure actual temperature using a thermometer at each of the duct temperature sensors. Compare this value to the appropriate scan tool Duct Actual parameter. The measured temperature should be within 5°C (9°F) difference of appropriate Duct Actual parameter value.
  4. If not within the specified range, refer to DTC B0173, B0178, B0509, B0514 or B3933
  5. Measure actual evaporator temperature using a thermometer. Compare this value to the scan tool A/C Evaporator Temperature Sensor parameter. The measured temperature should be within 5°C (9°F) difference of parameter value.
  6. If not within the specified range, refer to DTC B0173, B0178, B0509, B0514 or B3933
  7. Observe the scan tool Sunload parameter. The reading should be between 50-1 150 W/m² and change with sunlight intensity.
  8. If not within the specified range or not change, refer to DTC B0163, B0183, or B1405
  9. Engine is running, activate and deactivate the A/C switch. Verify the A/C compressor can be activated and deactivated.
  10. If the A/C compressor cannot be activated or deactivated, refer to Air Conditioning Compressor Malfunction
  11. Verify the engine reaches its operating temperature.

Circuit/System Testing

Only C68

  1. Ignition ON, turn the left temperature knob in all positions. Verify the scan tool Left Temperature Knob Position parameter. The reading should be between -5 to +5 and change with the knob position. At the left end position the reading should be 18 and at the right end position -18.
  2. If not the specified value, replace the A26 HVAC Control
  3. If all circuits test normal, replace the M6L Air Temperature Actuator - Left and verify the M6L Air Temperature Actuator - Left can be put into all positions. If the M6L Air Temperature Actuator - Left cannot be put into all positions, replace the K33 HVAC Control Module.

Only CJ2

  1. Ignition ON, turn the left temperature knob in all positions. Verify the scan tool Left Temperature Knob Position parameter. The reading should be between -5 to +5 and change with the knob position. At the left end position the reading should be 18 and at the right end position -18.
  2. If not the specified value, replace the A26 HVAC Control
  3. Ignition ON, turn the right temperature knob in all positions. Verify the scan tool Right Temperature Knob Position parameter. The reading should be between -5 to +5 and change with the knob position. At the left end position the reading should be 18 and at the right end position -18.
  4. If not the specified value, replace the A26 HVAC Control
  5. Verify the M6L Air Temperature Actuator - Left can be put into all positions.
  6. If the M6L Air Temperature Actuator - Left cannot be put into all positions, replace the M6L Air Temperature Actuator - Left and verify the M6L Air Temperature Actuator - Left can be put into all positions. If the M6L Air Temperature Actuator - Left cannot be put into all positions, replace the K33 HVAC Control Module.
  7. If all circuits test normal, replace the M6R Air Temperature Actuator - Right and verify the M6R Air Temperature Actuator - Right can be put into all positions. If the M6R Air Temperature Actuator - Right cannot be put into all positions, replace the K33 HVAC Control Module.

Repair Instructions

Perform the Diagnostic Repair Verification

    •  Temperature Valve Actuator Replacement - Left Side
    •  Temperature Valve Actuator Replacement - Right Side
    •  Heater and Air Conditioning Control Replacement
    •  Control Module References