Step | Action | Values | Yes | No | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
1 | Were you sent here from the A/C System Performance Test? | -- | Go to Step 2 | |||||||||||||
2 |
Caution: Refer to Moving Parts and Hot Surfaces Caution in the Preface section. Feel the liquid line before the expansion device. Is the liquid line cold before the expansion device? | -- | Go to Step 3 | Go to Step 8 | ||||||||||||
3 | Feel along the surfaces of the following high side components for a sudden drop in temperature (the high side components should feel warm/hot from the compressor all the way to the expansion device).
Is there an abrupt drop in temperature noted along the surfaces of any of the listed components? | -- | Go to Step 7 | Go to Step 4 | ||||||||||||
4 |
Is the liquid line extremely cold at the expansion device location and warm after the expansion device location? | -- | Go to Step 11 | Go to Step 5 | ||||||||||||
5 | Feel along the surfaces of the following low side components for a sudden change in temperature.
Is there an abrupt temperature change felt along the surfaces of any of the listed components? | -- | Go to Step 7 | Go to Step 6 | ||||||||||||
6 | Feel along the surfaces of low and high side components to compare the overall temperatures.
Are the overall temperatures of the low and high side components close to the same (both only mildly warm)? | -- | Go to Step 14 | Go to Step 8 | ||||||||||||
7 |
Is the repair complete? | -- | Go to Step 9 | -- | ||||||||||||
8 |
Is the weight of the recovered refrigerant charge equal to or above the specified value? | 0.57 kg (1.26 lb) | Go to Step 9 | Go to Step 9 | ||||||||||||
9 | Recharge the A/C system. Refer to Refrigerant Recovery and Recharging . Is the cooling performance improved? | -- | Go to Step 21 | Go to Step 10 | ||||||||||||
10 |
Is the repair complete? | -- | Go to Step 21 | -- | ||||||||||||
11 |
Are there metal flakes present? | -- | Go to Step 12 | Go to Step 13 | ||||||||||||
12 |
Is there a large amount of debris collected in the shop towel? | -- | Go to Step 18 | Go to Step 20 | ||||||||||||
13 | If the expansion device was restricted with a brown/black residue, perform the following:
Are the repairs complete? | -- | Go to Step 21 | -- | ||||||||||||
14 |
Is there debris present in the compressor suction port? | -- | Go to Step 15 | Go to Step 19 | ||||||||||||
15 |
Is there evidence of damage or debris? | -- | Go to Step 17 | Go to Step 16 | ||||||||||||
16 | If the expansion device does not show any signs of damage or debris:
Is there a large amount of debris collected in the shop towel? | -- | Go to Step 18 | Go to Step 19 | ||||||||||||
17 |
Are there metal flakes present? | -- | Go to Step 12 | Go to Step 13 | ||||||||||||
18 | If there was a large amount of debris collected in the shop towel from the compressor hose assembly;
Is the repair complete? | -- | Go to Step 19 | -- | ||||||||||||
19 | Install the suction and discharge lines. Refer to Suction Hose Replacement and Discharge Hose Replacement . Are the repairs complete? | -- | Go to Step 21 | -- | ||||||||||||
20 |
Are the repairs complete? | -- | Go to Step 21 | -- | ||||||||||||
21 | Record the low and high side pressures and the IP outlet air temperature after repairs are performed. Compare the pressures and outlet temperature to those listed in the A/C Performance Chart. Refer to Air Conditioning (A/C) System Performance Test . Are the readings within the specified ranges? | -- | Go to Step 22 | |||||||||||||
22 | Operate the system in order to verify the repair. Did you correct the condition? | -- | System OK | Go to Symptoms - HVAC Systems - Manual in HVAC Systems Manual. |