Step | Action | Yes | No |
---|---|---|---|
1 |
Is vacuum present? | Go to Step 2 | Go to Step 5 |
2 | Using a vacuum pump, apply vacuum to each actuator line at the HVAC Programmer Vacuum Line Connector. Do all the lines hold vacuum? | Go to Step 3 | Go to Step 4 |
3 | Inspect the actuator doors for binding. Did you find and correct the condition? | Go to Step 7 | Go to Step 6 |
4 | Inspect each vacuum line for an open or restriction, if no open or restriction was found replace the appropriate actuator. | Go to Step 7 | -- |
5 | Locate condition and restore vacuum to source line. | Go to Step 7 | -- |
6 | Replace the HVAC Programmer. | Go to Step 7 | -- |
7 | Operate the system in order to verify the repair. Did you correct the condition? | System OK | -- |