Table 1: | A/C Performance Table |
This test measures the operating efficiency of the A/C system under the following conditions:
• | The current ambient air temperature |
• | The current relative humidity |
• | The high side pressure of the A/C system |
• | The low side pressure of the A/C system |
• | The temperature of the air being discharged into the passenger compartment |
The numbers below refer to the step numbers on the diagnostic table.
This step determines if the A/C system has at least the minimum refrigerant charge required to operate the system without damage.
This step measures the performance of the A/C system.
This step is to allow for vehicle variations as well as high ambient temperatures.
Step | Action | Values | Yes | No | ||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Important:
| ||||||||||||||||||||||||||||||
Are both the low side and high side pressures within the specified value? | More than 16°C (60°F) - 345 kPa (50 psi) More than 24°C (75°F) - 483 kPa (70 psi) More than 33°C (90°F) - 690 kPa (100 psi) | Go to Step 2 | Go to Leak Testing | |||||||||||||||||||||||||||
Important: Record the relative humidity and the ambient air temperature at the time of the test.
Important: Press the RESET button, before using the print function of the J 43600 .
Does all the data recorded fall within the specified ranges of the A/C Performance Table below? | -- | Go to Step 8 | Go to Step 3 | |||||||||||||||||||||||||||
If the pressures and temperatures recorded do not fall within the specified ranges:
Does all the data recorded fall within the specified ranges of the table below? | -- | Go to Step 8 | Go to Step 4 | |||||||||||||||||||||||||||
4 | Do the high and low side pressures fall within the specified ranges, but the panel outlet temperatures do not? | -- | Go to Step 5 | |||||||||||||||||||||||||||
5 | Is the low side pressure greater than the specified range, but the high side pressure within or less than the specified range? | -- | Go to Step 6 | |||||||||||||||||||||||||||
6 | Are the low and high side pressures both greater than the specified ranges? | -- | Go to Step 7 | |||||||||||||||||||||||||||
7 | Is the high side pressure greater than the specified range, but the low side pressure is within or less than the specified range? | -- | Go to Step 8 | |||||||||||||||||||||||||||
8 | Operate the system in order to verify the test results. Did you find the same results? | -- | System OK | Go to Symptoms - HVAC Systems - Automatic or |
Ambient Temperature | Relative Humidity | Low Side Service Port Pressure | High Side Service Port Pressure | Maximum Left Center Discharge Air Temperature |
---|---|---|---|---|
13-18°C (55-65°F) | 0-100% | 150-215 kPa (22-31 psi) | 1050-1370 kPa (148-199 psi) | 10°C (50°F) |
19-24°C (66-75°F) | Less than 40% | 150-182 kPa (22-26 psi) | 1120-1430 kP (163-245 psi) | 6°C (43°F) |
Greater than 40% | 150-228 kPa (22-33 psi) | 1190-1470 kP (173-250 psi) | 10°C (50°F) | |
25-29°C (76-85°F) | Less than 35% | 150-200 kPa (22-29 psi) | 1330-1570 kPa (193-228 psi) | 8°C (46°F) |
35-50% | 150-210 kPa (22-30 psi) | 1350-1570 kPa (190-228 psi) | 9°C (48°F) | |
Greater than 60% | 153-231 kPa (22-34 psi) | 1360-1560 kPa (190-226 psi) | 11°C (52°F) | |
30-35°C (86-95°F) | Less than 30% | 150-228 kPa (22-33 psi) | 1490-1750 kPa (200-254 psi) | 10°C (50°F) |
30-50% | 156-230 kPa (22-33 psi) | 1490-1720 kPa (216-250 psi) | 11°C (52°F) | |
Greater than 50% | 170-233 kPa (25-34 psi) | 1490-1670 kPa (216-242 psi) | 12°C (54°F) | |
36-41°C (96-105°F) | Less than 20% | 186-264 kPa (27-38 psi) | 1700-1960 kPa (247-284 psi) | 14°C (57°F) |
20-40% | 187-255 kPa (27-37 psi) | 1690-1900 kPa (245-276 psi) | 13°C (55°F) | |
Greater than 40% | 189-246 kPa (27-36 psi) | 1660-1840 kPa (241-267 psi) | 13°C (55°F) | |
42-46°C (106-115°F) | Less than 20% | 229-296 kPa (33-43 psi) | 1910-2120 kPa (277-308 psi) | 17°C (63°F) |
Greater than 20% | 224-277 kPa (33-40 psi) | 1880-2040 kPa (273-305 psi) | 16°C (61°F) | |
47-49°C (116-120°F) | Below 30% | 256-312 kPa (37-45 psi) | 2040-2230 kPa (296-324 psi) | 19°C (66°F) |