Caution: Do not operate the detector in a combustible atmosphere since its sensor
operates at high temperature. Personal injury or damage to the equipment may
result.
Important: Vehicles equipped with an early warning system for low refrigerant may
set low refrigerant codes.
Perform a refrigerant leak test on the system whenever a leak is suspected.
Suspect leakage when a system indication of a low charge occurs or after
any service operation which disturbs the following items:
Halogen Leak Detector
Tools Required
• | J 39183-C 23 kg
(50 lb) Refillable Recovery Tank |
The halogen leak detector is the most useful tool in locating refrigerant
leaks. TheJ 39400
is
a small unit that operates on 12 V DC. The J 39400
provides an audible signal. The signal
increases in frequency when R-12 or R-134a is detected. There are three
settings:
Use the gross leak setting for isolating very large leaks already found
in one of the other two settings.
Ensure that the instrument is correctly calibrated according the instrument's
instructions. Ensure that the detector is set correctly for the type of refrigerant
system being tested.
Before you begin the test, ensure that the refrigerant system is sufficiently
charged for leak testing by measuring the static pressure with a gage set.
Readings in the range 413 to 689 kPa (60 to 100 psig)
are acceptable to conduct a leak test.
The most common leaks are found at the refrigerant fittings or connections.
Any of the following items may cause leaks:
• | Lack of lubricant on the O-rings |
• | Dirt/debris across the O-ring |
A small piece of lint from cotton gloves or shop cloths can create a
leak path across an O-ring.
The successful use of this and any other electronic leak detector depends
on the scan rate. It also depends on carefully following the manufacturer's
instructions regarding the following items:
Completely circle each joint. Move the leak detector at a rate of 1-2 inches
per second with the tip of the probe as close to the surface as possible.
Ensure that the tip of the probe is no more than 0.8 cm (0.25 in)
from the surface and does not block air intake.
A leak is indicated when the audible tone goes from a steady 1-2
clicks per second to a solid alarm. Adjust the balance knob frequently
in order to maintain the 1-2 clicks per second rate.
Important: Halogen leak detectors are sensitive to the following items:
• | Windshield washing solutions |
Important: Always follow the refrigerant system around in a continuous path. Do
not miss any areas of potential leaks. Test all of the areas in order to
ensure that the entire system is leak free, even when a leak was already
found.
Clean all of the surfaces in order to prevent a false warning. Ensure
that all surfaces are dry since ingestion of liquids will damage the detector.
The following items may be tested using this procedure:
• | Low and high side sensors |
• | Transducers and switches |
• | Evaporator inlet and outlet |
• | Accumulator dryer inlet and outlet |
• | Condenser inlet and outlet |
• | All brazed and welded areas |
• | Areas showing signs of damage |
Fluorescent Leak Detector
Tools Required
• | J 41459 R-134a
A/C Tracer Dye Injector |
R-134a refrigerant is uniquely different from the R-12 refrigerant that
was used in the past. R-134a may require additional methods to detect leaks.
The R-134a molecule is smaller than the R-12 molecule and can leak
through smaller openings. Also, R-134a does not contain chlorine, which
the electronic leak detectors found easy to identify. The tracer dye
method is meant to be used in conjunction with the electronic leak
detector. The tracer dye method will pinpoint smaller leaks that would not
be detected by using the electronic leak detector alone. R-134a tracer
dye requires time. Depending upon the rate of leak, it may take up
to 7 days for the leak to become visible.
Important:
• | The J 41447
has been developed to be used only with R-134aa equipped vehicles or vehicles
that have been retrofitted from R-12 to R-134a. |
• | Only J 41447
R-134a Tracer Dye is recommended for use in the R-134a system. Use of any
other products may affect system reliability and cause premature compressor
failure. |
• | Use only a 7.4 ml (.25 oz) ounce charge of tracer
dye. Larger amounts may compromise the reliability of the A/C system. |
• | After adding tracer dye, clean service valves and surfaces of
residual dye with GM Engine Degreaser GM P/N 1050436 or the equivalent in
order to prevent false diagnosis. |
Dye Injection
• | Charged systems can be injected with tracer dye by using J 41459
along with the instructions
provided. |
• | Discharged systems can have the tracer dye added to a replaced
component, or can be added using the ACR4 unit. |
Liquid Leak Detectors and Pressure Testing
Liquid/bubbles leak detectors have very limited usefulness. This is
due to the restricted visibility in refrigerant systems and the lack of sensitivity
in liquid/bubbles leak detectors.
Service Ports/Access Valves
The primary seal for the service ports is the sealing cap. This cap
contains a specially designed O-ring or gasket which provides a leak-free
seal. Loss of refrigerant charge will occur in the following situations:
One of the most difficult leaks to find is in the evaporator
core. Follow the instructions below in order to lead test the core:
- Turn the blower fan on high for 15 or more seconds.
- Shut the blower fan off.
- Wait 10 minutes.
- Remove the blower fan power module or resistor block if accessible.
- If the blower fan power module is not accessible, inspect the
condenser drain tube for moisture.
- If the condenser drain tube is dry, use the drain tube.
- Insert the leak detector probe into the resistor/relay opening,
or the blower case drain tube. If the detector goes to a solid alarm, a leak
has been found.
- Inspect the core face for evidence of refrigerant oil with a flashlight.
On R-134a systems, the lubricant is water soluble so no evidence of oil is
likely, even with a leak.
Compressor Shaft Seal
- Blow shop air behind and in front of the compressor clutch/pulley
for at least 15 seconds.
- Wait for 1-2 minutes.
- Probe the area in front of the pulley. If the detector goes to
a solid alarm, a leak has been found.