Step | Action | Value(s) | Yes | No |
---|---|---|---|---|
1 |
Is the measured voltage within the specified range? | 4-6 V | Go to Step 2 | Go to Step 3 |
2 | Replace the ambient outside temperature sensor. Refer to Ambient Temperature Sensor Replacement . Is the repair complete? | -- | System OK | -- |
3 |
Does the test lamp light? | -- | Go to Step 4 | Go to Step 5 |
4 | Locate and repair a short to ground in circuit 735 (LT GRN/BLK) between connector C 120 and the ambient outside air temperature sensor. Is the repair complete? | -- | System OK | -- |
5 |
Does the test lamp light? | -- | Go to Step 6 | Go to Step 7 |
6 | Locate and repair a short to ground in circuit 735 (LT GRN/BLK) between the heater-A/C control module assembly and connector 120. Is the repair complete? | -- | System OK | -- |
7 | Replace the heater-A/C control. Refer to Control Assembly Replacement . Is the repair complete? | -- | System OK | -- |