• | Perform the Diagnostic System Check - Vehicle prior to using this diagnostic procedure. |
• | Review Strategy Based Diagnosis for an overview of the diagnostic approach. |
• | Diagnostic Procedure Instructions provides an overview of each diagnostic category. |
Circuit | Short to Ground | Open/High Resistance | Short to Voltage | Signal Performance |
---|---|---|---|---|
Blower Motor Speed Control Circuit | 1, 2 | 1 | 1, 2 | -- |
Blower Motor Control Processor B+ | 1 | 1 | -- | -- |
Blower Motor Control Processor Ground | -- | 1 | 1 | -- |
Blower Motor Low Reference Circuit | 2 | 1 | 1 | -- |
1. Blower Motor Inoperative 2. Blower Motor Always On |
The blower motor control processor is an interface between the HVAC control module and the blower motor. The blower motor speed control, battery positive and ground circuits enable the control processor to operate. The HVAC control module provides a pulse width modulation (PWM) signal to the blower motor speed control processor in order to command the blower motor speed. The processor supplies 12 volts to the blower motor through the blower motor voltage supply circuit. The control processor uses the blower motor ground as a low side control to adjust the blower motor speed.
Be sure the blower motor housing is not shorted to a grounded surface causing the blower motor to run continuously at high speed.
Control Module References for scan tool information
⇒ | If the display does not change, replace the HVAC control module. |
⇒ | If greater than the specified range, test the ground circuit for an open/high resistance. |
⇒ | If the test lamp does not illuminate, test the B+ circuit for a short to ground or an open/high resistance. If the circuit tests normal and the B+ circuit fuse is open, replace the blower motor control processor. |
⇒ | If the test lamp is always OFF, test the ground circuit for a short to voltage or an open/high resistance. If the circuit tests normal, replace the blower motor control processor. |
⇒ | If the test lamp is always ON, test the ground circuit for a short to ground. If the circuit tests normal, replace the blower motor control processor. |
⇒ | If the test lamp is always OFF, test the control circuit for a short to ground or an open/high resistance. If the circuit tests normal, replace the blower motor control processor. |
⇒ | If the test lamp does not change intensity, test the control circuit for a short to voltage. If the circuit tests normal, replace the blower motor control processor. |
⇒ | If the blower motor does not activate, replace the blower motor. |
Perform the Diagnostic Repair Verification after completing the diagnostic procedure.
• | Control Module References HVAC control module replacement, setup, and programming |