Degrees* | Suction* | Discharge* | Outlet* |
---|---|---|---|
21°C (70°F) | 200-213 kPa (29-31 psi) | 723-916 kPa (105-133 psi) | 5-8°C (41-46°F) |
27°C (80°F) | 193-207 kPa (28-31 psi) | 999-1102 kPa (145-160 psi) | 6-7°C (42-45°F) |
33°C (90°F) | 186-200 kPa (27-29 psi) | 1275-1791 kPa (185-260 psi) | 7-8°C (45-47°F) |
38°C (100°F) | 179-193 kPa (26-28 psi) | 1550-2136 kPa (225-310 psi) | 8-9°C (46-48°F) |
Important: Statements contain additional information to help you confirm your diagnosis and lead you to a corrective action. When ALL pressure and temperature readings fall within the ranges of a given chart, use that chart to repair the vehicle.Key: Statements are used to interpret the pressure and temperature readings compared to normal system performance. If testing above or below ambient temperatures listed, rely on key statements to diagnose system. *Degrees - If the ambient air temperature is *Suction - and the low side gage should read *Discharge - and the high side gage should read *Outlet - and the right center air temperature should be |
Degrees* | Suction* | Discharge* | Outlet* |
---|---|---|---|
21°C (70°F) | 200-213 kPa (29-31 psi) | 723-916 kPa (105-133 psi) | 5-8°C (41-46°F) |
27°C (80°F) | 193-207 kPa (28-30 psi) | 999-1102 kPa (145-160 psi) | 6-7°C (42-45°F) |
33°C (90°F) | 186-200 kPa (27-29 psi) | 1275-1791 kPa (185-260 psi) | 7-8°C (45-47°F) |
38°C (100°F) | 179-193 kPa (26-28 psi) | 1550-2136 kPa (225-310 psi) | 8-9°C (46-48°F) |
*Degrees - If the ambient air temperature is *Suction - and the low side gage should read *Discharge - and the high side gage should read *Outlet - and the right center air temperature should be |
Important: To ensure accurate pressure and temperature readings make sure the vehicle is properly set up to run the performance test. Refer to vehicle set up section in this manual. ALL TEST PARAMETERS MUST BE FOLLOWED TO OBTAIN ACCURATE READINGS. Confirm system performance by touching the suction and discharge pipes at the compressor. The suction pipe will be cold and the discharge pipe will be hot.
Important: Use a refrigerant identifier to verify refrigerant purity. Non-condensable gases or refrigerant substitutes will affect system pressure/temperature readings.
Degrees* | Suction* | Discharge* | Outlet* |
---|---|---|---|
21°C (70°F) | 207-227 kPa (30-33 psi) | 593-675 kPa (86-98 psi) | 6-11°C (42-52°F) |
27°C (80°F) | 207-213 kPa (30-31 psi) | 758-827 kPa (110-120 psi) | 6-14°C (43-57°F) |
33°C (90°F) | 207-213 kPa (30-31 psi) | 1054-1171 kPa (153-170 psi) | 7-9°C (45-49°F) |
38°C (100°F) | 193-213 kPa (28-31 psi) | 1206-1378 kPa (175-200 psi) | 7-11°C (45-52°F) |
*Degrees - If the ambient air temperature is *Suction - and the low side gage should read *Discharge - and the high side gage should read *Outlet - and the right center air temperature should be |
Degrees* | Suction* | Discharge* | Outlet* |
---|---|---|---|
21°C (70°F) | 200-207 kPa (29-30 psi) | 758-999 kPa (110-145 psi) | 8-9°C (47-48°F) |
27°C (80°F) | 193-200 kPa (28-29 psi) | 1054-1206 kPa (153-175 psi) | 7-8°C (44-46°F) |
33°C (90°F) | 186-200 kPa (27-29 psi) | 1337-1929 kPa (194-280 psi) | 8-9°C (47-49°F) |
38°C (100°F) | 179-193 kPa (26-28 psi) | 1702-2412 kPa (247-350 psi) | 10-11°C (50-51°F) |
• | High humidity conditions affect the system performance by increased heat load on the system. This extra heat load will increase the discharge pressure and the outlet temperature. High humidity is defined as a relative humidity higher than 70 percent at 21°C (70°F), 60 percent at 27°C (80°F), 50 percent at 32°C (90°F), and 40 percent at 38°C (100°F). |
• | This chart illustrates the effect the high humidity has on the Saturn air conditioning system. Use this chart to determine the normal system performance under high humidity conditions. |
• | As a general rule, normal system operating under high humidity conditions will produce an outlet temperature of at least 20°F below the ambient air temperature. |
Degrees* | Suction* | Discharge* | Outlet * | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
21-38°C (70-100°F) | Normal to High | Low | Slightly Cool to Warm | ||||||||||
Important: The system is operating with a low charge.
Key: Poor Cooling at Higher Ambients. *Degrees - If the ambient air temperature is *Suction - and the low side gage should read *Discharge - and the high side gage should read *Outlet - and the right center air temperature should be |
Degrees* | Suction* | Discharge* | Outlet* | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
21-38°C (70-100°F) | Normal to Slightly High | High | Cool to Warm | ||||||||||
Important: The System may be operating in an overcharged condition.
Key: The high pressure switch cycles the compressor on and off at high ambient air temperatures *Degrees - If the ambient air temperature is *Suction - and the low side gage should read *Discharge - and the high side gage should read *Outlet - and the right center air temperature should be |
Degrees* | Suction* | Discharge* | Outlet* | ||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
21-38°C (70-100°F) | 483-689 kPa (70-100 psi) | 483-689 kPa (70-100 psi) | 21-38°C (70-100°F) | ||||||||
Important: Ensure that the manifold gage set valves are closed. Important: Most likely the vanes are not extending to the cylinder walls.
Key: No change in the suction and the discharge pressures with the compressor engaged. The gage pressures will be almost equal. *Degrees - If the ambient air temperature is *Suction - and the low side gage should read *Discharge - and the high side gage should read *Outlet - and the right center air temperature should be |
Degrees* | Suction* | Discharge* | Outlet* | ||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
21°C (70°F) | 289-338 kPa (42-49 psi) | 668-792 kPa (97-115 psi) | 15-18°C (59-65°F) | ||||||||
27°C (80°F) | 317-365 kPa (46-53 psi) | 827-930 kPa (120-135 psi) | 17-20°C (63-68°F) | ||||||||
33°C (90°F) | 379-434 kPa (55-63 psi) | 937-1275 kPa (136-185 psi) | 21-26°C (69-79°F) | ||||||||
38°C (100°F) | 434-482 kPa (63-70 psi) | 1109-1412 kPa (161-205 psi) | 23-29°C (73-84°F) | ||||||||
Important: The compressor may be at minimum displacement.
Key: Increased suction pressure for a relatively low discharge pressure and high outlet temperatures. |
Degrees* | Suction* | Discharge* | Outlet* | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
21°C (70°F) | 69-103 kPa (10-15 psi) | 930-1068 kPa (135-155 psi) | 5-1°C (23-34°F) | ||||||||||
27°C (80°F) | 76-131 kPa (11-19 psi) | 1275-1378 (185-200 psi) | 1-4°C (31-40°F) | ||||||||||
33°C (90°F) | 124-158 kPa (18-23 psi) | 1378-1585 kPa (200-230 psi) | 2-7°C (35-45°F) | ||||||||||
38°C (100°F) | 152-186 kPa (22-27 psi) | 1592-2480 kPa (231-360 psi) | 6-9°C (43-48°F) | ||||||||||
Important: The compressor may be at maximum displacement.
Key: Lower than normal suction pressure and outlet temperature at lower ambients and higher than normal discharge pressures. *Degrees - If the ambient air temperature is *Suction - and the low side gage should read *Discharge - and the high side gage should read *Outlet - and the right center air temperature should be |
Degrees* | Suction* | Discharge* | Outlet* | ||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
21°C (70°F) | 179-193 kPa (26-28 psi) | 710-744 kPa (103-108 psi) | 18-22°C (65-72°F) | ||||||||
27°C (80°F) | 179-200 kPa (26-29 psi) | 868-1034 kPa (126-150 psi) | 8-18°C (47-65°F) | ||||||||
33°C (90°F) | 165-186 kPa (24-27 psi) | 1096-1550 kPa (159-225 psi) | 7-16°C (44-61°F) | ||||||||
38°C (100°F) | 165-179 kPa (24-26 psi) | 1364-1895 kPa (198-275 psi) | 9-14°C (48-57°F) | ||||||||
Important: The degree of restriction will alter temperature and pressure readings. Important: The thermal expansion valve (TXV) may be restricted.
Key: Low suction pressure and higher than normal outlet air temperatures. *Degrees - If the ambient air temperature is *Suction - and the low side gage should read *Discharge - and the high side gage should read *Outlet - and the right center air temperature should be |
Degrees* | Suction* | Discharge* | Outlet* | ||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
21°C (70°F) | 200-213 kPa (29-31 psi) | 861-937 kPa (125-136 psi) | 6-9°C (42-49°F) | ||||||||
27°C (80°F) | 186-220 kPa (27-32 psi) | 1171-1344 kPa (170-195 psi) | 7-12°C (45-54°F) | ||||||||
33°C (90°F) | 193-234 kPa (28-34 psi) | 1364-1516 kPa (198-220 psi) | 9-14°C (48-57°F) | ||||||||
38° (100°F) | 234-303 kPa (34-44 psi) | 1543-2170 kPa (224-315 psi) | 15-17°C (59-63°F) | ||||||||
Important: The thermal expansion valve (TXV) may be open.
Key: Higher than normal suction pressure, and higher than normal outlet temperatures. *Degrees - If the ambient air temperature is *Suction - and the low side gage should read *Discharge - and the high side gage should read *Outlet - and the right center air temperature should be |
Degrees* | Suction* | Discharge* | Outlet* | ||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
21-38°C (70-100°F) | 0-34 kPa (0-5 psi) | 482-689 kPa (70-100 psi) | 21-38°C (70-100°F) | ||||||||
Important: The thermal expansion valve (TXV) may be closed.
Key: Near vacuum for suction pressure, low discharge pressure, and right center air grill near ambient. *Degrees - If the ambient air temperature is *Suction - and the low side gage should read *Discharge - and the high side gage should read *Outlet - and the right center air temperature should be |
Degrees* | Suction* | Discharge* | Outlet* | ||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
21-38°C (70-100°F) | Low | Low | Cool to Warm | ||||||||
Important: Confirm the condition by a thorough physical and visual inspection of all lines
and components.
Key: Temperature drop across restriction in line or component *Degrees - If the ambient air temperature is *Suction - and the low side gage should read *Discharge - and the high side gage should read *Outlet - and the right center air temperature should be |
Degrees* | Suction* | Discharge* | Outlet* |
---|---|---|---|
21°C (70°F) | 179-213 kPa (26-29 psi) | 958-1275 kPa (139-185 psi) | 5-8°C (41-46°F) |
27°C (80°F) | 172-207 kPa (25-28 psi) | 1309-1516 kPa (190-220 psi) | 6-9°C (42-48°F) |
33°C (90°F) | 172-200 kPa (25-27 psi) | 1550-2343 kPa (225-340 psi) | 7-9°C (45-48°F) |
38°C (100°F) | 172-200 kPa (25-27 psi) | 1895-2343 kPa (275-340 psi) | 7-12°C (45-53°F) |
*Degrees - If the ambient air temperature is *Suction - and the low side gage should read *Discharge - and the high side gage should read *Outlet - and the right center air temperature should be |
Important: To ensure accurate pressure and temperature readings make sure the vehicle is properly set up to run the performance test. Refer to vehicle set up section in this manual. ALL TEST PARAMETERS MUST BE FOLLOWED TO OBTAIN ACCURATE READINGS. Confirm system performance by touching the suction and discharge pipes at the compressor. The suction pipe will be cold and the discharge pipe will be hot.
Important: Use a refrigerant identifier to verify refrigerant purity. Non-condensable gases or refrigerant substitutes will affect system pressure/temperature readings.
Degrees* | Suction* | Discharge* | Outlet* |
---|---|---|---|
21°C (70°F) | 207-220 kPa (30-32 psi) | 634-827 kPa (92-120 psi) | 6-9°C (42-48°F) |
27°C (80°F) | 200-213 kPa (29-31 psi) | 806-1034 kPa (117-150 psi) | 7-10°C (44-50°F) |
33°C (90°F) | 193-207 kPa (28-30 psi) | 999-1206 kPa (145-175 psi) | 6-11°C (43-51°F) |
38°C (100°F) | 193-207 kPa (28-30 psi) | 1275-1378 kPa (185-200 psi) | 6-13°C (43-55°F) |
Degrees* | Suction* | Discharge* | Outlet* |
---|---|---|---|
21°C (70°F) | 186-193 kPa (27-28 psi) | 978-1378 kPa (142-200 psi) | 7-8°C (44-46°F) |
27°C (80°F) | 193-200 kPa (28-29 psi) | 1275-1585 kPa (185-230 psi) | 8-9°C (46-49°F) |
33°C (90°F) | 186-193 kPa (27-28 psi) | 1640-2480 kPa (238-360 psi) | 9-11°C (49-52°F) |
38°C (100°F) | 186-200 kPa (27-29 psi) | 1991-2515 kPa (289-365 psi) | 11-13°C (52-56°F) |
*Degrees - If the ambient air temperature is *Suction - and the low side gage should read *Discharge - and the high side gage should read *Outlet - and the right center air temperature should be |
• | High humidity conditions affect the system performance by increased heat load on the system. This extra heat load will increase the discharge pressure and the outlet temperature. High humidity is defined as a relative humidity higher than 70 percent at 21°C (70°F), 60 percent at 27°C (80°F), 50 percent at 32°C (90°F), and 40 percent at 38°C (100°F). |
• | This chart illustrates the effect the high humidity has on the Saturn air conditioning system. Use this chart to determine the normal system performance under high humidity conditions. |
• | As a general rule, normal system operating under high humidity conditions will produce an outlet temperature of at least 20°F below the ambient air temperature. |
Degrees* | Suction* | Discharge * | Outlet * | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
21-38°C (70-100°F) | Normal to High | Low | Slightly Cool to Warm | ||||||||||
Important: The system is operating with a low charge.
Key: Poor Cooling at Higher Ambients. *Degrees - If the ambient air temperature is *Suction - and the low side gage should read *Discharge - and the high side gage should read *Outlet - and the right center air temperature should be |
Degrees* | Suction* | Discharge* | Outlet* | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
21-38°C (70-100°F) | Normal to Slightly High | High | Cool to Warm | ||||||||||
Important: The System may be operating in an overcharged condition.
Key: The high pressure switch cycles the compressor on and off at high ambient air temperatures. |
Degrees* | Suction* | Discharge* | Outlet* | ||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
21-38°C (70-100°F) | 483-689 kPa (70-100 psi) | 483-689 kPa (70-100 psi) | 21-38°C (70-100°F) | ||||||||
Important: Ensure that the manifold gage set valves are closed. Important: Most likely the vanes are not extending to the cylinder walls.
Key: No change in the suction and the discharge pressures with the compressor engaged. The gage pressures will be almost equal. *Degrees - If the ambient air temperature is *Suction - and the low side gage should read *Discharge - and the high side gage should read *Outlet - and the right center air temperature should be |
Degrees* | Suction* | Discharge* | Outlet* | ||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
21°C (70°F) | 317-358 kPa (46-52 psi) | 717-861 kPa (104-125 psi) | 17-21°C (62-69°F) | ||||||||
27°C (80°F) | 358-400 kPa (52-58 psi) | 854-1171 kPa (124-170 psi) | 18-23°C (64-73°F) | ||||||||
33°C (90°F) | 400-455 kPa (58-66 psi) | 1013-1240 kPa (147-180 psi) | 21-26°C (70-79°F) | ||||||||
38°C (100°F) | 455-565 kPa (66-82 psi) | 1144-1550 kPa (166-225 psi) | 27-32°C (81-90°F) | ||||||||
Important: The compressor may be at minimum displacement.
Key: Increased suction pressure for a relatively low discharge pressure and high outlet temperatures. *Degrees - If the ambient air temperature is *Suction - and the low side gage should read *Discharge - and the high side gage should read *Outlet - and the right center air temperature should be |
Degrees* | Suction* | Discharge* | Outlet* | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
21°C (70°F) | 110-124 kPa (16-18 psi) | 1164-1240 kPa (169-180 psi) | 3-6°C (37-42°F) | ||||||||||
27°C (80°F) | 138-158 kPa (20-23 psi) | 1378-1654 (200-240 psi) | 3-8°C (37-46°F) | ||||||||||
33°C (90°F) | 165-172 kPa (24-25 psi) | 1598-2274 kPa (232-330 psi) | 6-9°C (42-49°F) | ||||||||||
38°C (100°F) | 179-186 kPa (26-27 psi) | 1902-2412 kPa (276-350 psi) | 8-11°C (46-51°F) | ||||||||||
Important: The compressor may be at maximum displacement.
Key: Lower than normal suction pressure and outlet temperature at lower ambients and higher than normal discharge pressures. *Degrees - If the ambient air temperature is *Suction - and the low side gage should read *Discharge - and the high side gage should read *Outlet - and the right center air temperature should be |
Degrees* | Suction* | Discharge* | Outlet* | ||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
21°C (70°F) | 200-213 kPa (27-29 psi) | 806-1068 kPa (117-155 psi) | 11-12°C (51-53°F) | ||||||||
27°C (80°F) | 172-200 kPa (25-27 psi) | 1123-1378 kPa (163-200 psi) | 8-11°C (47-52°F) | ||||||||
33°C (90°F) | 158-179 kPa (23-26 psi) | 1337-1929 kPa (194-280 psi) | 9-13°C (49-55°F) | ||||||||
38° (100°F) | 165-179 kPa (24-26 psi) | 1660-2412 kPa (241-350 psi) | 9-14°C (48-58°F) | ||||||||
Important: The degree of restriction will alter temperature and pressure readings. Important: The thermal expansion valve (TXV) may be restricted.
Key: Low suction pressure and higher than normal outlet air temperatures. *Degrees - If the ambient air temperature is *Suction - and the low side gage should read *Discharge - and the high side gage should read *Outlet - and the right center air temperature should be |
Degrees* | Suction* | Discharge* | Outlet* | ||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
21°C (70°F) | 186-207 kPa (27-30 psi) | 1123-1178 kPa (163-171 psi) | 8-11°C (47-51°F) | ||||||||
27°C (80°F) | 193-220 kPa (28-32 psi) | 1282-1309 kPa (186-190 psi) | 9-12°C (48-54°F) | ||||||||
33°C (90°F) | 220-255 kPa (32-37 psi) | 1447-1723 kPa (210-250 psi) | 8-17°C (47-63°F) | ||||||||
38° (100°F) | 248-317 kPa (36-46 psi) | 1778-2136 kPa (258-310 psi) | 14-18°C (58-64°F) | ||||||||
Important: The thermal expansion valve (TXV) may be open.
Key: Higher than normal suction pressure, and higher than normal outlet temperatures. *Degrees - If the ambient air temperature is *Suction - and the low side gage should read *Discharge - and the high side gage should read *Outlet - and the right center air temperature should be |
Degrees* | Suction* | Discharge* | Outlet* | ||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
21-38°C (70-100°F) | 0-34 kPa (0-5 psi) | 482-689 kPa (70-100 psi) | 21-38°C (70-100°F) | ||||||||
Important: The thermal expansion valve (TXV) may be closed.
Key: Near vacuum for suction pressure, low discharge pressure, and right center air grill near ambient. *Degrees - If the ambient air temperature is *Suction - and the low side gage should read *Discharge - and the high side gage should read *Outlet - and the right center air temperature should be |
Degrees* | Suction* | Discharge* | Outlet* | ||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
21-38°C (70-100°F) | Low | Low | Cool to Warm | ||||||||
Important: Confirm the condition by a thorough physical and visual inspection of all lines
and components.
Key: Temperature drop across restriction in line or component. *Degrees - If the ambient air temperature is *Suction - and the low side gage should read *Discharge - and the high side gage should read *Outlet - and the right center air temperature should be |