• | Perform the Diagnostic System Check - Vehicle prior to using this diagnostic procedure. |
• | Review Strategy Based Diagnosis for an overview of the diagnostic approach. |
• | Diagnostic Procedure Instructions provides an overview of each diagnostic category. |
Circuit | Short to Ground | High Resistance | Open | Short to Voltage |
---|---|---|---|---|
Recirculation Door Control CircuitĀ A | 1 | 1 | 1 | 1 |
Recirculation Door Control CircuitĀ B | 1 | 1 | 1 | 1 |
5-Volt Reference | 1 | 1 | 1 | 1 |
Recirculation Door Position Signal | -- | 1 | 1 | 1 |
Recirculation Actuator Low Reference | 1 | 1 | -- | |
B+ circuit of the HVAC control module | 1 | 1 | 1 | -- |
Ground circuit of the HVAC control module | -- | 1 | 1 | -- |
1. Recirculation Actuator Inoperative |
The recirculation actuator is a 5-wire bi-directional electric motor that incorporate a feedback potentiometer. Low reference, 5-volt reference, position signal, and 2 control circuits enable the actuators to operate. The control circuits use either a 0 or 12-volt value to coordinate the actuator movement. When the actuator is at rest, both control circuits have a value of 0 volts. In order to move the actuator, the HVAC control module grounds one of the control circuits while providing the other with 12 volts. The HVAC control module reverses the polarity of the control circuits to move the actuator in the opposite direction. This gives the actuator the power to adjust the air source being used from fresh air to recirculation (cabin air). When the actuator shaft rotates, the potentiometer's adjustable contact changes the door position signal between 0-5 volts.
Control Module References for Scan Tool Information
The scan tool air in let commanded counts parameter should change.
⇒ | If greater than 1.0 ohm, test the low reference circuit for an open/high resistance. If the circuit tests normal, replace the HVAC control module. |
⇒ | If less than 4.8 volts, test the 5-volt reference circuit for a short to ground or an open/high resistance. If the circuit tests normal, replace the HVAC control module. |
⇒ | If greater than 5.2 volts, test the 5-volt reference circuit for a short to voltage. If the circuit tests normal, replace the HVAC control module. |
⇒ | If greater than the specified range, test the signal circuit terminal 2 for a short to ground. If the circuit tests normal, replace the HVAC control module. |
⇒ | If less than the specified range, test the signal circuit for a short to voltage or an open/high resistance. If the circuit tests normal, replace the HVAC control module. |
⇒ | If the test lamp remains always ON or always OFF during either commands, test for an open, short to ground, or short to voltage on either control circuit. If the circuit tests normal, replace the HVAC control module. |
Perform the Diagnostic Repair Verification after completing the diagnostic procedure.
• | Control Module References for HVAC replacement, setup, and programming. |