• | Perform the Diagnostic System Check - Vehicle prior to using this diagnostic procedure. |
• | Review Strategy Based Diagnosis for an overview of the diagnostic approach. |
• | Diagnostic Procedure Instructions provides an overview of each diagnostic category. |
Circuit | Short to Ground | Open/High Resistance | Short to Voltage | Signal Performance |
---|---|---|---|---|
Recirculation 5-Volt Reference | B0228 02 , B0413 02 , B0423 02, B0433 02, B0228 02, B3782 02 or B3779 02 | B0228 05 | B0228 02, B0413 02, B0423 02, B0433 02, B0228 02, B3782 02 or B3779 02 | B0228 61 |
Recirculation Door Position Signal | B0228 02 | B0228 05 | B0228 05 | B0228 61 |
Recirculation Door Control A | B0228 02 | B0228 05 | B0228 05 | B0228 61 |
Recirculation Door Control B | B0228 02 | B0228 05 | B0228 05 | B0228 61 |
Recirculation Low Reference | B0228 02 | B0228 05 | B0228 05 | B0228 61 |
Driver Air Temperature 5-Volt Reference | B0228 02, B0413 02, B0423 02, B0433 02, B0228 02, B3782 02 or B3779 02 | B0413 05 | B0228 2, B0413 02, B0423 02, B0433 02, B0228 02, B3782 02 or B3779 02 | B0413 61 |
Driver Air Temperature Door Position Signal | B0413 02 | B0413 05 | B0413 05 | B0413 61 |
Driver Air Temperature Door Control A | B0413 02 | B0413 05 | B0413 05 | B0413 61 |
Driver Air Temperature Door Control B | B0413 02 | B0413 05 | B0413 05 | B0413 61 |
Driver Air Temperature Low Reference | B0413 02 | B0413 05 | B0413 05 | B0413 61 |
Passenger Air Temperature 5-Volt Reference | B0228 02, B0413 02, B0423 02, B0433 02, B0228 02, B3782 02 or B3779 02 | B0423 05 | B0228 02, B0413 02, B0423 02, B0433 02, B0228 02, B3782 02 or B3779 02 | B0423 61 |
Passenger Air Temperature Door Position Signal | B0423 02 | B0423 05 | B0423 05 | B0423 61 |
Passenger Air Temperature Door Control A | B0423 02 | B0423 05 | B0423 05 | B0423 61 |
Passenger Air Temperature Door Control B | B0423 02 | B0423 05 | B0423 05 | B0423 61 |
Passenger Air Temperature Low Reference | B0423 02 | B0423 05 | B0423 05 | B0423 61 |
Mode 5-Volt Reference | B0228 02, B0413 02, B0423 02, B0433 02, B0228 02, B3782 02 or B3779 02 | B3779 05 | B0228 02, B0413 02, B0423 02, B0433 02, B0228 02, B3782 02 or B3779 02 | B3779 61 |
Mode Door Position Signal | B3779 02 | B3779 05 | B3779 05 | B3779 61 |
Mode Door Control A | B3779 02 | B3779 05 | B3779 05 | B3779 61 |
Mode Door Control B | B3779 02 | B3779 05 | B3779 05 | B3779 61 |
Mode Low Reference | B3779 02 | B3779 05 | B3779 05 | B3779 61 |
Auxiliary Air Temperature 5-Volt Reference | B0228 02, B0413 02, B0423 02, B0433 02, B0228 02, B3782 02 or B3779 02 | B0433 05 | B0228 02, B0413 02, B0423 02, B0433 02, B0228 02, B3782 02 or B3779 02 | B0433 61 |
Auxiliary Air Temperature Door Position Signal | B0433 02 | B0433 05 | B0433 05 | B0433 61 |
Auxiliary Air Temperature Door Control A | B0433 02 | B0433 05 | B0433 05 | B0433 61 |
Auxiliary Air Temperature Door Control B | B0433 02 | B0433 05 | B0433 05 | B0433 61 |
Auxiliary Air Temperature Low Reference | B0433 02 | B0433 05 | B0433 05 | B0433 61 |
Auxiliary Mode 5-Volt Reference | B0228 02, B0413 02, B0423 02, B0433 02, B0228 02, B3782 02 or B3779 02 | B3782 05 | B0228 2, B0413 02, B0423 02, B0433 02, B0228 02, B3782 02 or B3779 02 | B3782 61 |
Auxiliary Mode Door Position Signal | B3782 02 | B3782 05 | B3782 05 | B3782 61 |
Auxiliary Mode Door Control A | B3782 02 | B3782 05 | B3782 05 | B3782 61 |
Auxiliary Mode Door Control B | B3782 02 | B3782 05 | B3782 05 | B3782 61 |
Auxiliary Mode Low Reference | B3782 02 | B3782 05 | B3782 05 | B3782 61 |
The actuators operate using 5 circuits. A 5-volt reference, low reference, signal circuit and two bi-directional 0 or 12-volt control circuits. The HVAC control module supplies a low reference and 5-volt reference to the potentiometer. The HVAC control module monitors the voltage drop across the potentiometer on the door position signal circuit. As the actuator door changes position the door position signal circuit voltage also changes. The two bi-directional control circuits enable the actuator to operate. Both circuits are set to 0 volts when the HVAC control module detects, from the feedback potentiometer, that the actuator is in the desired position. In order to move the actuator, the HVAC control module switches the appropriate control circuit to 12 volts.
• | DTC B0228 is for the recirculate actuator |
• | DTC B0413 is for the left air temperature actuator |
• | DTC B0433 is for the auxiliary air temperature actuator |
• | DTC B3782 is for the auxiliary mode actuator |
• | DTC B3779 is for the mode actuator |
• | The ignition is ON. |
• | The HVAC module is ON. |
The actual door position differs from the commanded door position by more than 4 counts or the HVAC control module detects the door position signal circuit is less than 3 counts or greater than 253 counts.
The control circuit is deactivated for the appropriate actuator.
• | The DTC becomes history when the HVAC control module no longer detects the condition that set the DTC. |
• | The history DTC will clear after 100 fault-free ignition cycles. |
Control Module References for Scan Tool Information
Ignition ON, command the appropriate actuator in both directions with a scan tool. The reading should be between 3 and 253 counts.
⇒ | If greater than the specified range, test the low reference circuit for an open/high resistance. If the circuit tests normal, replace the HVAC control module. |
⇒ | If less than the specified range, test the 5-volt reference circuit for a short to ground or an open/high resistance. If the circuit tests normal, replace the HVAC control module. |
⇒ | If greater than the specified range, test the 5-volt reference circuit for a short to voltage. If the circuit tests normal, replace the HVAC control module. |
⇒ | If less than the specified range, test the signal circuit terminal 9 for a short to ground. If the circuit tests normal, replace the HVAC control module. |
⇒ | If greater than the specified range, test the signal circuit for a short to voltage or an open/high resistance. If the circuit tests normal, replace the HVAC control module. |
⇒ | If greater than the specified range, test the control circuit for a short to voltage or an open/high resistance. If circuit tests normal, replace the HVAC control module. |
⇒ | If greater than the specified range, test the control circuit for a short to voltage or an open/high resistance. If circuit tests normal, replace the HVAC control module. |
⇒ | If the test lamp remains OFF during either of the commands, test for a short to ground on either control circuit. If the circuits test normal, replace the HVAC control module. |
Perform the Diagnostic Repair Verification after completing the diagnostic procedure.
• | Control Module References for HVAC control module and HVAC Auxiliary control module or rear seat audio (RSA) replacement, setup, and programming. |