Remove the expansion valve (3) from the evaporator.
Connect the expansion valve (3) to a J 39183-C
. Connect the gauge
set charging hose to a Refrigerant-134a refrigerant drum (2).
Soak the valve's remote bulb in water.
Close both the high pressure valve and the low pressure valve.
Open the valve to the refrigerant drum.
Open the high pressure valve to approximately 5 kg/cm²
(70 psi).
Read the pressure indicated on the low pressure gauge (5).
Measure the water temperature with a thermometer.
The pressure/temperature relationship should
fall within the specifications shown in the table. If the pressure/temperature
does not fall into the specifications, replace the expansion valve.