- Install
the air temperature door to the HVAC module assembly upper case.
- Install the right and left air temperature actuators to the HVAC module
assembly upper case.
Notice: Use the correct fastener in the correct location. Replacement fasteners
must be the correct part number for that application. Fasteners requiring
replacement or fasteners requiring the use of thread locking compound or sealant
are identified in the service procedure. Do not use paints, lubricants, or
corrosion inhibitors on fasteners or fastener joint surfaces unless specified.
These coatings affect fastener torque and joint clamping force and may damage
the fastener. Use the correct tightening sequence and specifications when
installing fasteners in order to avoid damage to parts and systems.
- Install the screws that secure the right and left air temperature actuators
to the HVAC module assembly upper case.
Tighten
Tighten the screws to 1.5 N·m (13 lb in).
- From the inside of the upper case, drill the dimples adjacent to the heat
stakes using a 5.5 mm (7/32 in) drill bit.
- Align and attach the upper and lower HVAC
module assembly case.
- Install the removed screws that secure the HVAC module assembly upper
case to the HVAC module assembly lower case to their original position.
Tighten
Tighten the screws to 1.5 N·m (13 lb in).
- Install new screws that will secure the HVAC module assembly upper case
to the HVAC module assembly lower case in the locations adjacent to the heat stakes
that were removed.
Tighten
Tighten the screws to 1.5 N·m (13 lb in).
- Connect the right and left air temperature electrical connector to the
air temperature actuators.
- Install the mode actuator.
- Install the screws that secure the mode actuator to the HVAC module assembly.
Tighten
Tighten the screws to 1.5 N·m (13 lb in).
- Connect the mode actuator electrical connector to the mode actuator.
- Install the recirculation housing to the HVAC module assembly.
- Install the screws that secure the recirculation housing to the HVAC module
assembly.
Tighten
Tighten the screws to 1.5 N·m (13 lb in).
- Route the recirculation actuator harness through the recirculation housing
clips.
- Connect the recirculation actuator electrical connector to the recirculation
actuator.
Important: Do not adjust any controls on the HVAC control module while the HVAC control
module is calibrating. If interrupted improper HVAC performance will result.
- Install the HVAC module assembly. Refer to
HVAC Module Assembly Replacement
.