Step | Action | Value(s) | Yes | No | ||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
1 | Did you review the HVAC blower operation and perform the necessary inspections? | -- | Go to Step 2 | Go to Symptoms | ||||||||
2 |
Does the blower motor produce heated, then cooled air? | -- | Go to Testing for Intermittent Conditions and Poor Connections | Go to Step 3 | ||||||||
3 |
Does the blower motor produce heated air? | 60 kPa (8.7 lb/sq in) | Go to Step 4 | Go to Step 15 | ||||||||
4 |
Does the vacuum gauge indicate a vacuum greater than the specified value? | 60 kPa (8.7 lb/sq in) | Go to Step 7 | Go to Step 5 | ||||||||
5 |
Does the vacuum gauge indicate a vacuum greater than the specified value? | 60 kPa (8.7 lb/sq in) | Go to Step 6 | Go to Step 17 | ||||||||
6 |
Is air flow present at the water valve? | -- | Go to Step 28 | Go to Step 19 | ||||||||
7 |
Does the test lamp light? | -- | Go to Step 8 | Go to Step 20 | ||||||||
8 | Connect a J 39200 digital multimeter (DMM) between valve actuator motor connector cavity 7 for CKT 150 (BLK) and ground. Refer to Circuit Testing in Wiring Systems. Does the circuit have continuity? | -- | Go to Step 9 | Go to Step 21 | ||||||||
9 |
Is voltage present and does it vary? | -- | Go to Step 22 | Go to Step 10 | ||||||||
10 |
Does the test lamp light? | -- | Go to Step 11 | Go to Step 24 | ||||||||
11 |
Does the circuit have continuity? | -- | Go to Step 12 | Go to Step 25 | ||||||||
12 | Connect a J 35616-200 unpowered test lamp between heater and A/C controller connector C2 cavity F for CKT 733 (LT BLU) and ground. Refer to Circuit Testing in Wiring Systems. Does the test lamp light? | -- | Go to Step 26 | Go to Step 13 | ||||||||
13 | Connect a J 39200 DMM between heater and A/C controller connector C2 cavity F for CKT 733 and ground. Refer to Circuit Testing in Wiring Systems. Does the circuit have continuity? | -- | Go to Step 27 | Go to Step 14 | ||||||||
14 | Connect a J 39200 DMM between heater and A/C controller connector C2 cavity F and temperature valve actuator motor connector cavity 8 for CKT 733 (LT BLU). Refer to Circuit Testing in Wiring Systems. Does the circuit have continuity? | -- | Go to Step 28 | Go to Step 29 | ||||||||
15 | Inspect the engine coolant flow through the heater core for any restriction. Is the engine coolant flow path open? | -- | Go to Step 16 | Go to Heating Insufficient | ||||||||
16 | Replace the water valve. Refer to Heater Water Valve Replacement . Is the repair complete? | -- | Go to Step 30 | -- | ||||||||
17 | Inspect the vacuum supply from the engine to the heater for the following conditions:
Did you find and correct a condition with the engine vacuum supply? | -- | Go to Step 30 | Go to Step 18 | ||||||||
18 | Check the engine for a mechanical condition which might cause low vacuum. Refer to the appropriate section:
Did you find and correct the condition? | -- | Go to Step 30 | Go to Step 3 | ||||||||
19 | Inspect the white/black vacuum tube from the heater and A/C controller to the water valve for the following conditions:
Did you find and correct a vacuum condition? | -- | Go to Step 30 | -- | ||||||||
20 | Repair the open in CKT 141 (BRN) between the instrument panel fuse block and the temperature valve actuator motor connector. Refer to Wiring Repairs in Wiring Systems. Is the repair complete? | -- | Go to Step 30 | -- | ||||||||
21 | Repair the open in CKT 150 (BLK) between the temperature valve actuator motor and ground G201. Refer to Wiring Repairs in Wiring Systems. Is the repair complete? | -- | Go to Step 30 | -- | ||||||||
22 | Inspect the temperature valve door for any mechanical condition. Did you find and repair a mechanical condition with the temperature valve door? | -- | Go to Step 30 | Go to Step 23 | ||||||||
23 | Replace the temperature valve actuator motor. Refer to Temperature Actuator Replacement . Is the repair complete? | -- | Go to Step 30 | -- | ||||||||
24 | Repair the open in CKT 141 (BRN) between splice S215 and the heater and A/C controller. Refer to Wiring Repairs in Wiring Systems. Is the repair complete? | -- | Go to Step 30 | -- | ||||||||
25 | Repair the open in CKT 150 (BLK) between the heater and A/C controller connector and splice S202. Refer to Wiring Repairs in Wiring Systems. Is the repair complete? | -- | Go to Step 30 | -- | ||||||||
26 | Repair the short to voltage in CKT 733 (LT BLU) between the temperature valve actuator motor connector and the heater and A/C controller connector. Refer to Wiring Repairs in Wiring Systems. Is the repair complete? | -- | Go to Step 30 | -- | ||||||||
27 | Repair the short to ground in CKT 733 (LT BLU) between the temperature valve actuator motor connector and the heater and A/C controller connector. Refer to Wiring Repairs in Wiring Systems. Is the repair complete? | -- | Go to Step 30 | -- | ||||||||
28 | Replace the heater and A/C controller. Refer to Control Assembly Replacement . Is the repair complete? | -- | Go to Step 30 | -- | ||||||||
29 | Repair the open in CKT 733 (LT BLU) between the heater and A/C controller connector and the temperature valve actuator motor connector. Refer to Wiring Repairs in Wiring Systems. Is the repair complete? | -- | Go to Step 30 | -- | ||||||||
30 | Operate the heater and the A/C in order to verify the repair. Did you correct the condition? | -- | System OK | Go to Step 3 |