Table 1: | Gray Area Diagnosis and Service |
Table 2: | Striped Area Diagnosis and Service |
Step | Action | Value(s) | Yes | No | ||||
---|---|---|---|---|---|---|---|---|
1 | Connect the J 39500-B . Are the pressures greater than the specified values? | 350 kPa (50 psi) | Go to Step 2 | Go to Step 6 | ||||
2 | Inspect and correct for a blown Air Conditioner (A/C) fuse. Does the complaint persist? | Go to Step 3 | System OK | |||||
3 | Inspect and correct for the following conditions:
Refer to HVAC Compressor Clutch Does Not Engage . Does the complaint persist? | -- | Go to Step 4 | System OK | ||||
4 | Inspect and correct for the following conditions:
Refer to Engine Cooling. Does the complaint persist? | -- | Go to Step 5 | System OK | ||||
5 |
Does the complaint persist? | -- | Go to Step 8 | System OK | ||||
6 |
Did you find a leak? | -- | Go to Step 7 | System OK | ||||
7 |
Does the complaint persist? | -- | Go to Step 1 | System OK | ||||
8 | Perform an A/C Performance Check using the following steps:
Does the A/C performance meet the requirement on the Performance Chart? | 5°C (41°F) | Go to Step 9 | Go to HVAC High Side vs. Low Side Pressure Chart | ||||
9 | Was the customer complaint made due to high temperature and/or high humidity? | -- | Go to Step 10 | System OK | ||||
10 | Perform a leak test. Refer to Leak Testing . Did you find a leak? | -- | Go to Step 11 | System OK | ||||
11 | Recharge the A/C system. Refer to Refrigerant Recovery and Recharging . Does the complaint persist? | -- | Go to Step 8 | System OK |
Problem | Action | ||||||||
---|---|---|---|---|---|---|---|---|---|
Important: The V5 clutch may cycle if the discharge pressure exceeds 2758 kPa (400 psi). | |||||||||
Improper condenser operation | Improper condenser operation may result from one of the following causes:
| ||||||||
High side refrigerant restriction |
| ||||||||
Refrigerant system overcharged (high discharge and high suction pressures) | The clutch may cycle ON/OFF and cause compressor noise. Refer to air in system. | ||||||||
Expansion tube (orifice) blocked | Low suction pressures. | ||||||||
Air in system (High discharge and high suction pressures). |
|
Problem | Action | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
The compressor is damaged internally. |
| ||||||||||
The expansion tube (orifice) is missing. | Feel the liquid line after the expansion tube. If the line is warm, recover the refrigerant. Refer to Refrigerant Recovery and Recharging . Inspect the system for proper installation of the expansion tube. Refer to Expansion (Orifice) Tube Replacement . If the expansion tube or the O-ring is missing, replace the expansion tube. | ||||||||||
The compressor runs at minimum stroke. |
| ||||||||||
The compressor control valve is set improperly. | The low load test creates a low cooling load that causes the V5 compressor to go toward a minimum stroke. Minimum stroke is necessary in order to evaluate the control valve set point. Perform the low load test using the following procedure:
| ||||||||||
The refrigerant system is undercharged. |
| ||||||||||
The expansion tube (orifice) is blocked. |
|