Step | Action | Yes | No | ||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
1 | Were you sent here from the A/C System Performance Test? | ||||||||||
2 | After continued operation of the A/C system, do the low and high side pressures equalize or become static? | ||||||||||
3 | Refer to the pressures recorded during the A/C System Performance Test. Inspect for the following conditions: Caution: Refer to Moving Parts and Hot Surfaces Caution in the Preface section.
Do the listed conditions exist ? | ||||||||||
4 | Refer to the pressures recorded during the A/C System Performance Test. Inspect for the following conditions:
Do the listed conditions exist ? | ||||||||||
5 | The A/C system has a low refrigerant charge. Evacuate and recharge the A/C system. Refer to Refrigerant Recovery and Recharging . Is the procedure complete? | -- | |||||||||
6 |
Are the readings within the specified ranges? | ||||||||||
7 | The A/C compressor is malfunctioning. Remove the expansion device and inspect for contamination. Refer to Thermal Expansion Valve Replacement . Are there metal flakes on the expansion device? | ||||||||||
8 | Inspect the expansion device for a brown, powdery residue indicating desiccant in the A/C system. Is there a brown, powdery residue present? | ||||||||||
9 |
Is there metal flake contamination present? | ||||||||||
10 |
Is the repair complete? | -- | |||||||||
11 |
Is the repair complete? | -- | |||||||||
12 |
Is the repair complete? | -- | |||||||||
13 | Operate the system in order to verify the repair Did you correct the condition? | System OK |