Table 1: | Air Delivery Improper <<CJ2>> |
Table 2: | Vacuum/Electric Solenoid Scan Tool Data Display |
Step | Action | Value(s) | Yes | No | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
1 | Has the HVAC Diagnostic System Check been performed? | -- | Go to Diagnostic System Check | |||||||||||||||
2 |
Does the scan tool indicate the correct combination of vacuum/electric solenoids ON and OFF (shown in the table below) through all of the operating modes listed? | -- | ||||||||||||||||
3 |
Is the vacuum reading within the specified values? | 10-17 in.Hg | ||||||||||||||||
4 | Inspect and repair the leak or restriction in the purple vacuum supply line, vacuum tank, or the manifold vacuum line to the tank. Is the repair complete? | -- | -- | |||||||||||||||
5 |
If necessary turn the ignition ON and and blower motor to HIGH in order to verify door operation. Do the vacuum actuators hold vacuum and effectivly control door operation? | -- | ||||||||||||||||
6 | Inspect and repair or replace any sticking or binding door conditions, inoperative vacuum actuators, or vacuum supply lines. Refer to the following procedures: Is the repair complete? | -- | -- | |||||||||||||||
7 |
Does the test light illuminate? | -- | ||||||||||||||||
8 | Repair the open or high resistance in the voltage supply circuit 41. Is the repair complete? | -- | -- | |||||||||||||||
9 |
Does the test light illuminate only when the table below indicates each solenoid control circuit should be ON. | -- | ||||||||||||||||
10 | Test and repair the inoperative solenoid control circuits for the following conditions:
Did you find and correct the condition? | -- | ||||||||||||||||
11 | Replace the HVAC control solenoid valve. Refer to Vacuum Electrical Solenoid Replacement . Is the repair complete? | -- | -- | |||||||||||||||
12 | Replace the HVAC control assembly. Refer to Control Assembly Replacement . Is the repair complete? | -- | -- | |||||||||||||||
13 |
Did you correct the condition? | -- | System OK | Go to Diagnostic System Check |
Operating Mode | Solenoid 1 (Defroster Solenoid) | Solenoid 2 (Heater Solenoid) | Solenoid 3 (Mode Closed Soienoid) | Solenoid 4 (Air Inlet Solenoid) | Solenoid 5 (Mode Open Solenoid) |
---|---|---|---|---|---|
Upper | OFF | ON | OFF | N/A | ON |
Bi-Level | OFF | ON | OFF | N/A | OFF |
Lower | OFF | ON | ON | N/A | OFF |
Defog | OFF | OFF | ON | OFF | OFF |
Defrost | ON | OFF | ON | OFF | OFF |
Fresh Air | N/A | N/A | N/A | OFF | N/A |
Recirculate | N/A | N/A | N/A | ON | N/A |