Use the following diagnostic tables in order to diagnose insufficient cooling conditions with the following systems:
• | The V5 compressor |
• | The VDOT refrigerant system |
Use these procedures in conjunction with other appropriate service manual information.
The V5 compressor is a variable displacement compressor. The V5 compressor matches the air conditioning demand by changing the stroke instead of cycling the clutch. A control valve is located in the rear head of the compressor. The control valve senses compressor low side pressure and causes the compressor to change the stroke. Because the V5 compressor always runs and the system does not cycle, these diagnostic procedures differ from procedures used for fixed displacement systems. Use these procedures in order to avoid needlessly replacing the A/C components.
Repair the following components as needed. If the air discharge air temperature with the A/C ON is normal after repairing the following components, the system is operating properly:
• | The A/C fuse |
• | The A/C blower operation |
• | The temperature door |
Move the temperature door rapidly from the COLD position to the HOT position. Listen for the temperature door hitting at each end. Adjust the door as needed. (Cable-operated temperature door only) |
• | The clutch coil |
• | The rear head switch connections |
• | The drive belt |
Adjust the belt as needed. Replace the belt if the belt is damaged or missing. Refer to Drive Belt Replacement in Engine Mechanical 2.2L or Drive Belt Replacement . |
• | The engine cooling fan operation |
• | The condenser |
Inspect the condenser for restricted air flow. |
Consult Dealer Technical Bulletins and the Service Guild for updates on the A/C system.
Refer to the following diagnostic procedures:
Step | Action | Value(s) | Yes | No |
---|---|---|---|---|
1 |
Are both pressures below the specified value? | 345 kPa (50 psi) | Go to Step 2 | Go to Step 5 |
2 | Are both pressures within the specified range? | 69-345 kPa (10-50 psi) | Go to Step 3 | Go to Step 4 |
3 |
Are both pressures above the specified value? | 345 kPa (50 psi) | System OK | -- |
4 |
Are both pressures above the specified value? | 345 kPa (50 psi) | System OK | -- |
5 | Are both pressures above the specified value? | 345 kPa (50 psi) | System OK | -- |
Step | Action | Value(s) | Yes | No | ||||
---|---|---|---|---|---|---|---|---|
1 |
Does the clutch engage? | -- | Go to Step 2 | Go to Step 6 | ||||
2 | Inspect the system for the following conditions:
Does a slipping belt condition exist? | -- | Go to Step 3 | Go to Step 4 | ||||
3 | Tighten the belt as needed. Is the repair complete? | -- | Go to Step 4 | -- | ||||
4 | Does a compressor noise exist? | -- | Go to Step 5 | System OK | ||||
5 | Replace the compressor. Refer to Air Conditioning Compressor Replacement . Is the repair complete? | -- | System OK | -- | ||||
6 |
Does the clutch engage? | -- | Go to Step 7 | Go to Step 9 | ||||
7 | Repair the electrical circuit to the compressor clutch. Is the repair complete? | -- | Go to Step 8 | -- | ||||
8 |
Does the clutch engage? | -- | System OK | -- | ||||
9 | Replace the clutch coil. Is the repair complete? | -- | System OK | -- |
Important: This test is designed for the following garage conditions:
• 21-32°C (70-90°F) • No sun load
Step | Action | Value(s) | Yes | No | ||||
---|---|---|---|---|---|---|---|---|
1 |
Are both sides of the line the same temperature? | -- | Go to Step 2 | Go to Step 5 | ||||
2 | Recover the refrigerant. Refer to Refrigerant Recovery and Recharging . Is the orifice (expansion) tube missing? | -- | Go to Step 3 | Go to Step 4 | ||||
3 | Install the orifice (expansion) tube. Refer to Leak Testing . Is the repair complete? | -- | Go to Step 4 | -- | ||||
4 |
Is the discharge air temperature at least 7°C (20°F) cooler than the ambient temperature? | -- | System OK | Go to Step 1 | ||||
5 |
On engines with cycling cooling fans, record the pressures with the engine cooling fan ON. Do the low side and the high side pressures intersect in the striped area of the above chart? | -- | Go to Step 6 | Go to Step 15 | ||||
6 | Are the compressor high side and the low side pressures within 207 kPa (30 psi) of each other? | -- | Go to Step 7 | Go to Step 10 | ||||
7 |
Are the compressor high side and the low side pressures within 207 kPa (30 psi) of each other? | -- | Go to Step 8 | Go to Step 1 | ||||
8 |
Does the compressor clutch driver (not the pulley) turn freely by hand? | -- | Go to Step 9 | Go to | ||||
9 | Replace the compressor. Refer to Air Conditioning Compressor Replacement . Is the repair complete? | -- | Go to Step 1 | -- | ||||
10 | Is the low side pressure within the specified range? | 172-241 kPa (25-35 psi) | Go to Step 11 | Go to | ||||
11 | If the refrigerant is under-charged, add 0.40 kg (14 oz) of refrigerant to the system. Does the cooling performance improve? | -- | Go to Step 12 | Go to Step 13 | ||||
12 | Leak test the system. Refer to Leak Testing . Repair any leaks as needed. Are all necessary repairs complete? | -- | Go to Step 20 | -- | ||||
13 |
Is the tube plugged? | -- | Go to Step 14 | Go to Step 20 | ||||
14 |
If only light debris is present in the tube, clean the tube using compressed air. Are all necessary repairs complete? | -- | Go to Step 20 | -- | ||||
15 | Do the low side and high side pressures intersect in the grey area of the above chart? | -- | Go to Step 17 | Go to Step 16 | ||||
16 | The low side and high side pressures intersect in the normal (white) area of the above chart. Does insufficient cooling exist? | -- | Go to Air Delivery Improper | System OK | ||||
17 |
Is the line cold? | -- | Go to Step 18 | Go to Step 19 | ||||
18 | A restriction exists in the high side. Perform the following steps:
Is the line clear? | -- | Go to Step 20 | -- | ||||
19 | One of the following conditions exists:
Recover the refrigerant. Refer to Refrigerant Recovery and Recharging . Has the refrigerant been recovered? | -- | Go to Step 20 | -- | ||||
20 |
Are all of the procedures complete? | -- | Go to Step 1 | -- |
Step | Action | Value(s) | Yes | No |
---|---|---|---|---|
Important: Follow the steps in this test procedure exactly. This test is designed in order to create a low cooling load. This condition causes the V5 compressor to operate at less than full stroke. This condition is absolutely necessary in order to obtain accurate test results. | ||||
1 |
Is the low side pressure within the specified range? | 172-241 kPa (25-35 psi) | Go to Step 2 | |
2 |
Are all of the procedures complete? | -- | -- |